Combined Arresters – Type 1 + Type 2

                         DEHNventil M TN (FM)
        951 200   DV M TN 255
        951 205   DV M TN 255 FM
                         Modular combined lightning current and surge arrester for single-phase TN systems with a nominal voltage of 230 V (2+0 configuration);
        951 200   4013364108097  04 01 01 01   724 g
              620,50 €   FM version with floating remote signalling contact.
        951 205   4013364108103  04 01 01 01   668 g
              670,60 €
                          Type DV M ...                     TN 255                   TN 255 FM
                          Part No.                          951 200                  951 205
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 + type 2 / class I + class II   type 1 + type 2 / class I + class II
                          Max. continuous operating voltage (a.c.)  (UC)  264 V (50 / 60 Hz)   264 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs) [L+N-PE]  (Itotal)  50 kA  50 kA
                                                            25 kA
                                                                                     25 kA
                          Lightning impulse current (10/350 µs) [L, N-PE]  (Iimp)
    Combined Arresters – Type 1 + Type 2  Max. backup fuse (L) up to IK = 50 kArms  315 A gG  315 A gG
                          Voltage protection level [L-PE]/[N-PE]  (UP)
                                                                                     ≤ 1.5 / ≤ 1.5 kV
                                                            ≤ 1.5 / ≤ 1.5 kV
                          Approvals
                                                                                     KEMA, VDE, UL
                                                            KEMA, VDE, UL
                                                                                     changeover contact
                                                            —
                          Type of remote signalling contact
                                                            For use in switchgear installations with prospective short-circuit currents
                          Extended technical data:
                                                            of more than 50 kArms (tested by the German VDE)
                                                                                     100 kArms (220 kApeak)
                          – Max. prospective short-circuit current
                                                            100 kArms (220 kApeak)
                         DEHNventil M TT 2P (FM)
        951 110   DV M TT 2P 255
        951 115   DV M TT 2P 255 FM
                         Modular combined lightning current and surge arrester for single-phase TT and TN-S systems with a nominal voltage of 230 V
        951 110   4013364108110  04 01 01 01   659 g
              672,70 €   (1+1 configuration); FM version with floating remote signalling contact.
        951 115   4013364108127  04 01 01 01   664 g
              722,80 €
                          Type DV M ...                     TT 2P 255                TT 2P 255 FM
                          Part No.                          951 110                  951 115
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 + type 2 / class I + class II   type 1 + type 2 / class I + class II
                          Max. continuous operating voltage (a.c.) [L-N]  (UC)  264 V (50 / 60 Hz)   264 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs) [L+N-PE]  (Itotal)  50 kA  50 kA
                          Lightning impulse current (10/350 µs) [L-N]/[N-PE]  (Iimp) 25 / 50 kA  25 / 50 kA
                          Voltage protection level [L-N]/[N-PE]  (UP)  ≤ 1.5 / ≤ 1.5 kV   ≤ 1.5 / ≤ 1.5 kV
                          Max. backup fuse (L) up to IK = 50 kArms  315 A gG         315 A gG
                          Approvals                         KEMA, VDE, UL            KEMA, VDE, UL
                          Type of remote signalling contact  —                       changeover contact
                          Extended technical data:
                          Voltage protection level [L-PE]  (UP)  2.2 kV              2.2 kV
                                                            For use in switchgear installations with prospective short-circuit currents
                                                            of more than 50 kArms (tested by the German VDE)
                          – Max. prospective short-circuit current  100 kArms (220 kApeak)    100 kArms (220 kApeak)