Page 32 - Surge-Protection-E_0.pdf
P. 32

Combined Arresters – Type 1 + Type 2

                         DEHNshield TNC
        941 300   DSH TNC 255
                         Application-optimised and prewired combined lightning current and surge arrester for TN-C systems with a nominal voltage of 230 / 400 V
        941 300   4013364133556  04 01 01 04   386 g
              426,50 €   (3+0 configuration).
                          Type DSH ...                           TNC 255
                          Part No.                               941 300
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 + type 2 / class I + class II
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs) [L1+L2+L3-PEN]  (Itotal)  37.5 kA
                                                                 12.5 kA
                          Lightning impulse current (10/350 µs) [L-PEN]  (Iimp)
    Combined Arresters – Type 1 + Type 2  941 305   DSH TNC 255 FM  DEHNshield TNC FM  160 A gG
                                                                 ≤ 1.5 kV
                          Voltage protection level  (UP)
                          Max. mains-side overcurrent protection
                                                                 KEMA, VDE, UL
                          Approvals

                         Application-optimised and prewired combined lightning current and surge arrester for TN-C systems with a nominal voltage of 230 / 400 V
                         (3+0 configuration); with floating remote signalling contact.
             361 g
        941 305
         4013364275317  04 01 01 04


         465,90 €
                          Type DSH ...                           TNC 255 FM
                          Part No.                               941 305
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 + type 2 / class I + class II
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs) [L1+L2+L3-PEN]  (Itotal)  37.5 kA
                          Lightning impulse current (10/350 µs) [L-PEN]  (Iimp)  12.5 kA
                          Voltage protection level  (UP)         ≤ 1.5 kV
                          Max. mains-side overcurrent protection  160 A gG
                          Approvals                              KEMA, VDE
                          Type of remote signalling contact      changeover contact

                         DEHNshield TNC Basic FM
        941 306   DSH B TNC 255 FM
                         Application-optimised and prewired combined lightning current and surge arrester for TN-C systems for use in the main power supply system
        941 306   4013364328068  04 01 01 04   362 g   (3+0 configuration) in case of residential buildings without external lightning protection system (also in case of buildings supplied by over-
              311,30 €
                         head lines); with floating remote signalling contact.
                          Type DSH ...                           B TNC 255 FM
                          Part No.                               941 306
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 + type 2 / class I + class II
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs) [L1+L2+L3-PEN]  (Itotal)  22.5 kA
                          Lightning impulse current (10/350 µs) [L-PEN]  (Iimp)  7.5 kA
                          Voltage protection level  (UP)         ≤ 1.5 kV
                          Max. mains-side overcurrent protection  160 A gG
                          Approvals                              VDE
                          Type of remote signalling contact      changeover contact



                         DEHNshield TNS
        941 400   DSH TNS 255
                         Application-optimised and prewired combined lightning current and surge arrester for TN-S systems with a nominal voltage of 230 / 400 V
        941 400   4013364133563  04 01 01 04   525 g
              553,40 €   (4+0 configuration).
                          Type DSH ...                           TNS 255
                          Part No.                               941 400
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 + type 2 / class I + class II
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE]  (Itotal)  50 kA
                          Lightning impulse current (10/350 µs) [L, N-PE]  (Iimp)  12.5 kA
                          Voltage protection level [L-PE]/[N-PE]  (UP)  ≤ 1.5 / ≤ 1.5  kV
                          Max. mains-side overcurrent protection  160 A gG
                          Approvals                              KEMA, VDE, UL















        28               You will find detailed product information on our website             Valid as of August 1, 2020
   27   28   29   30   31   32   33   34   35   36   37