Combined Arresters – Type 1 + Type 2


           DEHNshield
           •  Application-optimised and prewired spark-gap-based type
            1 + type 2 combined lightning current and surge arrester
           •  Compact design due to space-saving spark gap technology
            with a width of only one module / pole
           •  Fulfils the minimum requirements on the lightning current
            discharge capacity according to IEC 60364-5-53
           •  Allows compact lightning equipotential bonding including
            protection of terminal equipment
           •  Discharge capacity up to 50 kA (10/350 µs)
           •  Operating state / fault indication by green / red indicator flag
            in the inspection window                                                                                  Combined Arresters – Type 1 + Type 2
           •  High follow current extinguishing capacity (Ifi = 25 kArms)











                                                                For protecting compact low-voltage consumer's installations against surges and
                                                                even direct lightning strikes. For installation in conformity with the lightning pro-
                                                                tection zone concept at the boundaries from 0A – 2.

           DaEHNshield TNC 255:   Application-optimised combined lightning current and surge arrester for TN-C systems
           DEHNshield TNS 255:   Application-optimised combined lightning current and surge arrester for TN-S systems
           DEHNshield TT 255:   Application-optimised combined lightning current and surge arrester for TT and TN-S systems (3+1 configuration)
           DEHNshield TN 255:    Application-optimised combined lightning current and surge arrester for single-phase TN systems
           DEHNshield TT 2P 255:   Application-optimised combined lightning current and surge arrester for single-phase TT and TN systems
                             (1+1 configuration)
           DEHNshield … FM:    With remote signalling contact for monitoring device (floating changeover contact)

           The space-saving and application-optimised DEHNshield family offers   The follow-current-limiting spark gap technology ensures selectivity with
           various benefits provided by type 1 + type 2 spark-gap-based arresters   regard to low-current-rated fuses (35 A gG). This means that upstream
           such as the “wave breaker function” (WBF). This function and the associ-  fuses will not trip due to mains follow currents.
           ated reduction of the pulse time mitigate the energy of the lightning im-  Busbars and pin-shaped terminals from DEHN can be used for connecting
           pulse current to an acceptable level for downstream protection stages or   DEHNshield to other DIN rail mounted devices. The type designation of
           terminal equipment. Moreover, DEHNshield arresters are directly energy   DEHNshield makes it easy to choose the right arrester for the relevant
           coordinated with other arresters of the Red/Line product family.  system configuration of the low-voltage consumer’s installation.
           Application-optimised DEHNshield combined lightning current and surge   The operating state / fault indicator of every protective path does not
           arresters combine lightning equipotential bonding up to lightning impulse   cause operating currents and instantly shows the operating state of the
           currents of 50 kA (10/350 µs) and surge protection in a single device.   arrester. Apart from the standard visual indicator with green and red indi-
           This clearly distinguishes DEHNshield from varistor-based arresters of this   cator flags, the DEHNshield ... FM versions feature a three-pole remote
           application and performance class.                   signalling terminal. As the remote signalling contact is designed as a float-
           Due to their technical parameters and the very compact design as spark-  ing changeover contact, the remote signal can, depending on the circuit
           gap-based arresters with only one module / pole, DEHNshield arresters   concept, be used as a make or break contact.
           are ideally suited for this application class. For this reason, they are a   Due to their parameters and design,
           space-saving and application-optimised solution in particular for residen-   DEHNshield devices can even be in-
           tial buildings.                                                              stalled upstream of meter panels in
           DEHNshield arresters also provide optimal protection in existing buildings   low-voltage consumer installations.
           without an external lightning protection system where roof superstruc-
           tures or overhead line supplies are installed which require type 1 SPDs
           according to VdS 2031.
           No additional backup fuse is required if an installation is protected by
           backup fuses up to 160 A.
           The energy-coordinated arresters even protect terminal equipment if the
           distance between DEHNshield and the consumers is ≤ 10 m. The non-ex-
           hausting spark gap and the small space requirements of the applica-  Series connection by means of a
           tion-optimised combined lightning current and surge arresters enable   lightning-current-tested STAK 25 pin-
           easy integration into distribution boards.           shaped terminal








           Valid as of August 1, 2020                         You will find detailed product information on our website   27
   26   27   28   29   30   31   32   33   34   35   36