Page 29 - Surge-Protection-E_0.pdf
P. 29
Combined Arresters – Type 1 + Type 2
Protection Module for DEHNventil modular
• High discharge capacity due to powerful creepage discharge
spark gap
• Maximum system availability due to RADAX Flow follow
current limitation
• Easy replacement of protection modules without tools due
to module locking system with module release button
• Operating state / fault indication by green / red indicator
flag in the inspection window
• The plug-in protection module can be replaced without the
need to de-energise and without removing the distribution
board cover Combined Arresters – Type 1 + Type 2
In multipole protective circuits, we recommend replacing the complete
set of protection modules when one module fails.
For protecting low-voltage consumer installations against surges and even direct
lightning strikes. For installation in conformity with the lightning protection zone
concept at the boundaries from 0A – 2.
DV MOD 255: Spark-gap-based protection module
DV MOD NPE 50: 50 kA N-PE spark-gap-based protection module
DV MOD NPE 100: 100 kA N-PE spark-gap-based protection module
The spark-gap-based protection modules of the modular DEHNventil se- Avoid additional, short-notice and unplanned maintenance jobs.
ries combine safety and innovation in a single device. Apart from the en- In multipole protective circuits, we recommend replacing the complete set
capsulated RADAX Flow spark gap technology, the compact protection of protection modules when one module fails.
modules incorporate the complete monitoring circuit for controlling the
energy flow of the spark gap, the monitoring device and the operating
state / fault indicator.
The mechanical coding of the protection module prevents that the N-PE
protection modules are confused with the spark-gap-based module for
the phase conductors.
The module locking mechanism fixes the protection modules to the base
part. Protection modules can be easily removed without tools by simply
pressing the module release button.
Spark-Gap-Based Protection Module 951 001 DV MOD 255
Spark-gap-based protection module for DEHNventil M ...
951 001 4013364108066 04 01 01 01 192 g
285,80 €
Type DV MOD ... 255
Part No. 951 001
Max. continuous operating voltage (a.c.) (UC) 264 V
Lightning impulse current (10/350 µs) (Iimp) 25 kA
N-PE Spark-Gap-Based Protection Module 951 050 951 100 DV MOD NPE 50
DV MOD NPE 100
N-PE spark-gap-based protection module for DEHNventil M ... with ... + 1 configuration.
951 050 4013364108073 04 01 01 01 171 g
951 100 338,00 € 4013364108080 04 01 01 01 171 g
Type DV MOD ... NPE 50 NPE 100
356,10 €
Part No. 951 050 951 100
Max. continuous operating voltage (a.c.) (UC) 255 V 255 V
Lightning impulse current (10/350 µs) (Iimp) 50 kA 100 kA
Valid as of August 1, 2020 You will find detailed product information on our website 25