Page 304 - V16 Catalogue Final
P. 304
MULTIFUNCTION METER SELECTION CHART - SOCOMEC
The Diris multifunction meters have a built-in electronic component (ASIC).
Developed specifically by SOCOMEC for the measurement functions to achieve very
high measurement accuracy.
Diris multi-function meters compliant with IEC 61557-12 which is a high-level standard
for all PMDs (Performance Monitoring Devices) that are designed to measure and
monitor electrical parameters in distribution networks. Compliance with IEC 61557-
12 ensures a high level of equipment performance, in terms of metrology, and the
mechanical and environmental aspects (EMC, temperature, etc.).
Energy Accuracy:
- Active energy, class 0.5S to IEC 62053-22.
- Reactive energy, class 2 to IEC 62053.23.
The Socomec Diris meters functions include;
- Metering, Measuring, Monitoring, Analysing, Communicating
The add-on modules can be used to upgrade the product functions at any time for measuring, reporting and communications functions.
Application network (3P, 3P+N and single-phase) A10 A20 A30/41 A40 Diris B-10 Diris B-30
LV LV LV/HV LV/HV LV LV
Measure*
Monitor** Monitor**
Function Measure* Monitor Measure* Analysis***
Analysis Analysis
Alarming
Multi-Measurement:
Current (3I, In) • • • • • •
Power factor -instantaneous 3PF , ΣPF • • • • • •
Active, reactive and apparent energy on 4 quadrants • • • • • •
(kWh, kvarh, kVAh)
Temperature measurement internal, extrnal via 3 PT100 • •
sensors - - • • optional Optional
Quality:
Total Harmonic distortion (THD 3I, 3V, 3U) • • • • • •
• • •
Individual harmonics U, V, I - - -
63 rd 63 rd 63 rd
Accuracy:
Current and Voltage 0.2% 0.2% 0.2% 0.2% - -
Active energy Class 0.5S 0.5S 0.5S 0.5S 0.5 (M+CT) 0.5 (M+CT)
Reactive energy Class 2 2 2 2 - -
Communications:
RS485 JBUS / MODBUS Protocol • • • • • •
Ethernet connection with Modbus TCP - - • • - -
Ethernet connection with RS485 gateway with Modbus • • • • • •
TCP via gateways via gateways via gateways via gateways
Input/output:
Output pulse configurable 1 1 2 2 - -
Digital Input / Out put - - - 3 I/P 2/2 2/2
Analogue Input / Out put - - 4 O/P 2 O/P 2/2 2/2
Status/pulse inputs - - - - 2 2
Characteristic:
Mounting DIN rail Panel Panel Panel DIN DIN
•
• • • •
Web Server - (only on
via gateways via gateways via gateways via gateways
48250501)
Remote Display Available • • • • • •
Auxiliary supply AC 110…277V AC 110…400V AC 110…400V AC 110…400V AC 110-230V AC 110-230V AC
Dimensions W x H x D (mm) 72 x 90 x 64 96 x 96 x 60 96 x 96 x 60 96 x 96 x 60 54 x 100 x 65 54 x 100 x 65
- A41, B10 & B30 have 4th CT inputs for measuring neutral on networks with harmonics disturbances.
* Measure: Basic. **Monitor: Intermediate. ***Analyse: Advanced.
296 V16-PM-R04 www.ipd.com.au Phone: 1300 556 601