Page 307 - V16 Catalogue Final
P. 307

MULTIFUNCTION METERS




        Features:                            DIRIS A-20
        - Accuracy class 0.5S to IEC62053-22.
        - User-friendly operation.            Description                                          Part No.        POWER
        - Detects wiring errors.              DIRIS A-20 multifunction meter,base unit             48250402      MONITORING
        - Panel mount: 96 x 96, IP52 (front panel).  Auxiliary supply: 110-400V AC, 120-350V DC
        - Large easy to read backlit LCD display.  Total harmonic distortion up to row 51.
        - 4 direct access keys - simple to operate.
        - Facility to add up to 3 plug-in modules.
        - Standard IEC 61557-12.


                                             PLUG-IN MODULES
                                              Description                                          Part No.
                                              Output                                               48250080
                                              1 digital output for kWh or kvarh pulses OR
                                              alarm OR command through RS485
                                              Communication                                        48250082
                                              RS485 communication module with
                                              MODBUS protocol
                                              Input/Output                                         48250083
                                              3input(information report from an external contact),
                                              1output (pulse or alarm)

                        DIRIS A-20
                                             STANDARD FUNCTIONS

                                              Connection
                                                CT .../5A

                                              Metering
                                                Active energy: +/- kWh.
                                                Reactive energy: +/- kvarh.
                                                Hours.

                                              Instantaneous RMS Values
                                                Current (3I, In).
                                                Voltage & frequency instanceous: 3V, 3U, F
                                                Active, reactive and apparent power, per phase and total (±3P, ±3Q, 3S, ±∑P, ±∑Q, ∑S).
                                                Power factor, per phase and total (3PF, ∑PF).
                                              Maximum Values
                                                Current (3I, In).

                                              Power Quality Measurements
                                                Harmonic distortion rate on current and voltage integrated up to 51st harmonic (THD 3I, 3V, 3U).

                                              Energy Measurement Precision
                                                Class 0.5s - IEC 62053-22 (Active energy).
                                                Class 2 - IEC 62053-23 (Reactive energy).
                                             - For current transformers (CT’s) refer to pages 325-331.





                                             - For CT shorting link terminals refer to page 322 & 549.











        Phone: 1300 556 601                            www.ipd.com.au                                  V16-PM-R04  299