Interface the module has three signaling leds:
Figure 52
LEDs Description
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module
Power
on and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes
per second): module on and communication with Trip unit absent
Indicate the status of the contacts of each output:
I 11, I 12 • off: contact open
• on: contact closed
Indicate the status of the contacts of each input:
O 11, O 12 • off: circuit open
• on: short circuit
Menu The specific configuration area will activate in the Settings - Modules menu if the Ekip Signalling 2K
module is detected correctly by Ekip Touch.
A specific menu containing the submenus of all the available and configurable inputs and outputs is
available for each Ekip Signalling 2K module detected by Ekip Touch.
Input parameters All the available inputs enable the following parameters to be configured:
Parameter Description Default
Defines whether the input is interpreted as ON by Ekip Touch when Active
Polarity
it is open (Active open) or when it is closed (Active Closed) closed
Minimum activation time of the input before status change is
recognized; the delay is given in seconds and can be set within
range: 0 s to 100 s, in 0.01 s steps
Delay NOTES: 0.1 s
• if the input is deactivated before this time has elapsed the
status change is not recognized
• if delay = 0 s status change must still be more than 300 µS
165 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 External electronic accessories | 13 - Ekip Signalling 2K