                          Interface the module has three signaling leds:

                                                             2                          1











                                    Figure 51
                                     LEDs           Description
                                                    Signals the on status and correct communication with Ekip Touch:
                                                     • off: module off
                                                     • on steady or flashing synchronized with the Power led of Ekip Touch: module
                                     Power
                                                    on and communication with Trip unit present.
                                                     • flashing not synchronized with the Power led of Ekip Touch (2 fast flashes
                                                    per second): module on and communication with Trip unit absent
                                                    Indicates the communication state:
                                     Link (1)        • off: incorrect connection, signal absent.
                                                     • on steady: connection correct
                                                    Indicates the communication state:
                                     Activity (2)    • off: no activity on line
                                                     • flashing: activity on line present (receiving and/or transmitting)




            Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
                                    is available in the Settings menu (page 35).
                                    The following communication parameters can be configured if the module has been correctly detected by
                                    Ekip Touch in the Settings-Modules menu:
                                     Parameter          Description                                      Default
                                     Enable             Switches communication between module and server on/off. Off
                                                        Defines whether the module has the dynamic (Off) or static
                                     Static IP address ON  (On) IP address.                              Off
                                                        If = On all the associated parameters are enabled
                                     Static address IP   Enables the static IP to be selected            0.0.0.0
                                     address
                                     Static Network Mask  Enables the subnet mask to be selected         0.0.0.0
                                                        When there are several subnets, enables the IP address of the
                                     Static Gateway address                                              0.0.0.0
                                                        node to which the module is connected to be selected
                                                        Allows the SNTP protocol for distribution of the clock and
                                     Enable SNTP client                                                  Off
                                                        synchronization signal to be enabled.
                                     SNTP Server Addr.  Allows the network server that supplies the SNTP to be set.  0.0.0.0
                                     Password           Code required to register module on Cloud        ---

























       160 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                    External electronic accessories | 12 - Ekip Com Hub