Interface the module has three signaling leds:
2 1
Figure 51
LEDs Description
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module
Power
on and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes
per second): module on and communication with Trip unit absent
Indicates the communication state:
Link (1) • off: incorrect connection, signal absent.
• on steady: connection correct
Indicates the communication state:
Activity (2) • off: no activity on line
• flashing: activity on line present (receiving and/or transmitting)
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
is available in the Settings menu (page 35).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter Description Default
Enable Switches communication between module and server on/off. Off
Defines whether the module has the dynamic (Off) or static
Static IP address ON (On) IP address. Off
If = On all the associated parameters are enabled
Static address IP Enables the static IP to be selected 0.0.0.0
address
Static Network Mask Enables the subnet mask to be selected 0.0.0.0
When there are several subnets, enables the IP address of the
Static Gateway address 0.0.0.0
node to which the module is connected to be selected
Allows the SNTP protocol for distribution of the clock and
Enable SNTP client Off
synchronization signal to be enabled.
SNTP Server Addr. Allows the network server that supplies the SNTP to be set. 0.0.0.0
Password Code required to register module on Cloud ---