Page 166 - MCCB-XT5
P. 166

ABB | SACE Tmax XT

                       Connections For references about the connection and terminals, please consult document 1SdM000005A1001 and
                                    1SdM000019A1002; use AWG 22-16 cables with 1.4 mm maximum outer diameter for the external cabling.
                                    To connect the module to Ekip Supply and Ekip Cartridge, please consult document 1SdH002009A1503.


                      Power supply Ekip Com Signalling 2K is supplied directly by the Ekip Supply module to which it is connected.
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence
                                           of auxiliary power supply



                              Input Ekip Touch can be configured so that the status of the inputs corresponds to actions or signals, with
                                    different programming options (page 165).
                                    The connection of each input (H11 and H12 for model 2K-1, H21 and H22 for model 2K-2, H31 and H32 for
                                    model 2K-3) must be made with reference to the common contacts (HC).
                                    The module permits two logic statuses, interpreted differently by Ekip Touch depending on the
                                    configuration selected for each contact:
                                                                                             Status detected by Trip
                                     State      Electrical condition  Contact configuration
                                                                                             unit
                                                                      Active open           ON
                                     Open       Circuit open  (1)
                                                                      Active closed         OFF
                                                                      Active open           OFF
                                     Closed     Short-circuit  (2)
                                                                      Active closed         ON

                                    (1)  R > 100 kΩ
                                    (2)  R (wiring + short circuit contact) <25 Ω


                            Output Ekip Touch can be configured so that the contacts of each output are closed or opened upon the
                                    occurrence of one or more events, with different programming options (page 165).
                                    The output of each module consists of 2 contacts (K11-K12 and K13-K14 for model 2K-1; K21-K22 and
                                    K23-K24 for model 2K-2; K31-K32 and K33-K34 for model 2K-3), which are isolated from the unit and from
                                    the other outputs, and have the following electrical characteristics:
                                     Characteristics                        Maximum limit  (1)
                                     Maximum switchable voltage             150 VDC / 250 VAC
                                                                            2 A @ 30 VDC, 0,8 A @ 50 VDC, 0,2 A @ 150 VDC,
                                     Breaking capacity
                                                                            4 A @ 250 VAC
                                     Dielectric strength between open contacts  1000 V AC (1 minute @ 50 Hz).
                                     Dielectric strength between each contact and   1000 V AC (1 minute @ 50 Hz).
                                     coil

                                    (1)  data relating to a resistive load































       164 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                 External electronic accessories | 13 - Ekip Signalling 2K