Page 163 - MCCB-XT5
P. 163

Continued from the previous page                               ABB | SACE Tmax XT
                                    The Remote FW update submenu enables the Firmware update function of the module to be managed;
                                    the following parameters are available:
                                     Parameter    Description                                         Default
                                                  Enables firmware update function of module to be remotely
                                     Enable                                                           OFF
                                                  activated/deactivated
                                                  The parameter is available when Enable = On and allows the
                                                  automatic update mode to be activated (On): in the presence
                                                  of new Firmware, this latter is updated automatically. If the
                                     Automatic    parameter is Off, updating must be performed in the Manual   OFF (manual)
                                                  mode: in the presence of new Firmware, the message Ekip
                                                  Com Hub FW Update appears in the status bar and updating is
                                                  performed via the Manual command.
                                                  This parameter is available when Enable= On, with Automatic=
                                     Start FW     Off configuration and when new Firmware is present (see
                                     update       description above); allows the Firmware update of the module to
                                                  run



                Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the
                                    module correctly:
                                     Information    Description
                                     SN and version  Identifier and SW version of the module
                                                    Address of the module, assigned to the module by a DHCP server at the time
                                                    of connection to the network in the case of configuration with a dynamic IP, or
                                     IP address     can be set via the menu in the event of a static IP
                                                        NOTE: without a DHCP server, the module automatically adopts a random
                                                        IP address within the 169.254.xxx.xxx range
                                                    Subnet mask; identifies the method for recognizing the subnet to which the
                                     Network Mask   modules belong and enables modules to be searched for within a defined set
                                                    of recipients.
                                                    IP address of the node to which the module is connected, in the presence of
                                     Gateway address
                                                    several subnets
                                                    Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal
                                     MAC address
                                                    to ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device



              Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Parameter    Description                                         Default
                                                  Allows the CRL (Certificate Revocation List) to be used to
                                     CRL Enable
                                                  ascertain whether the server certificate is valid
                                     Clock update
                                     hardening    Enables control of the time reference transmitted by the SNTP
                                     enable       server
                                     SNTP Server   Enables the position of the SNTP server to be set in relation to
                                     Location     the network in which the module is installed
                                     SNTP Time
                                     zone         Defines the time zone to be used for synchronism    +00:00
                                     SNTP Daylight  Used to select whether daylight saving time is present (ON) or
                                     Saving Time  not (OFF) in the country to which the synchronization time refers  OFF
                                                  Permits (Enabled ARP) the periodic generation of a Gratuitous
                                     Disable      ARP message, used by Ekip Connect to rapidly find the modules   ARP Enabled
                                     Gratuitous ARP
                                                  via Ethernet scan without knowing the IP address beforehand
                                     Cloud data   Enables/disables the function that collects and transmits the
                                     send enable  module data                                         OFF
                                     JSON data    Allows the compressed format of the JSON file sent to Cloud to
                                     compression  be selected (enable)                                Disabled







       161 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                    External electronic accessories | 12 - Ekip Com Hub
   158   159   160   161   162   163   164   165   166   167   168