Page 165 - MCCB-XT5
P. 165

ABB | SACE Tmax XT

       13 - Ekip Signalling 2K



                                    Ekip Signalling 2K is an accessory signaling module allowing programmable inputs/outputs to be
                                    managed.
                                    This module has:
                                     •  two contacts for output signals and relative status led
                                     •  two digital inputs and relative status led
                                     •  a Power led with the startup status of the module
                                    Accessories Ekip Cartridge and Ekip Supply are required in order to connect Ekip Signalling 2K to Ekip
                                    Touch (page 130, 131).



                            Models Three different Signalling 2K modules are available: Ekip Signalling 2K-1, Ekip Signalling 2K-2 and RELT -
                                    Ekip Signalling 2K-3.
                                    The modules are identical in terms of characteristics and installation methods, except for: display menus,
                                    cabling and addresses for system communication, which are specific for each module.
                                           NOTE: if different indications are not given, the information in the next chapter is valid for
                                           all three models
                                    The three modules can be connected at the same time to Ekip Touch so as to expand the potential of the
                                    unit (e.g. to increase the number of control outputs and inputs).
                                    Two of the three modules can be connected at the same time to Ekip Touch so as to expand the potential
                                    of the unit (e.g. to increase the number of control outputs and inputs).
                                           IMPORTANT: each Ekip Touch can be fitted with only one module per type. The configuration
                                           with two or three modules of the same model is not allowed (example: two Ekip Signalling
                                           2K-1 modules)

                                    RELT - Ekip Signalling 2K-3
                                    The RELT - Ekip Signalling 2k-3 module has a dedicated command (RELT Wizard) for auto-programming
                                    a set of trip unit parameters; The wizard ensures the activation of the 2I protection when the input of
                                    the RELT – Ekip Signalling 2k-3 module active. In addition, the 2I is placed in local model and the RELT
                                    module’s outputs are activated.
                                    Below is a complete list of the parameters configured by the command:
                                     Parameter             Configuration from RELT Wizard command       Page
                                     2I Protection  (1)    On; Threshold I31 = 1,5 In                   48
                                                           Delay ON=100 ms; Delay OFF=15s; Activation =
                                     2I Protection Function  dependent function; Function = RELT -  Ekip Signalling   48, 78
                                                           2K-3 Input 1 (I31)
                                     Input I31 (RELT - Ekip   Polarity = active closed; Delay = 0,1 s   164, 165
                                     Signalling 2K-3)
                                                           Signal source = 2I protection active; Delay = 0 s; Contact
                                     Output O31 and O32 (RELT
                                     - Ekip Signalling 2K-3)  type = NO; Self-latching = OFF; min Activation Time = 0  166
                                                           ms
                                     SwitchOnLocal Function  Function = 2I protection active; Delay = 0 s  78

                                    (1)  if Dual set is present, programming performed for both Set A and Set B

                                    The RELT setup Wizard can be found in the 2I protection menu and also the first time the trip unit is
                                    switched ON.
                                    In the case that the wizard is not executed (or is rejected during the initial trip unit start up), the
                                    functionality and the characteristic of the RELT – Ekip Signalling 2k-3 module will be as described in the
                                    following pages.














       163 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                 External electronic accessories | 13 - Ekip Signalling 2K