Page 205 - MCCB-XT5
P. 205
ABB | SACE Tmax XT
Input parameters The input can be configured in the Settings-Modules-Ekip Signalling 1K-Input menu:
Parameter Description Default
Defines whether the input is interpreted as ON by the Trip unit
Polarity Active closed
when it is open (Active open) or when it is closed (Active Closed)
Minimum activation time of the input before status change is
recognized; the delay is given in seconds and can be set within
range: 0 s to 100 s, in 0.01 s steps
Delay NOTES: 0.1 s
• status change is not recognized if the input deactivates
before this time has elapsed
• if delay = 0 s status change must still be more than 300 µS
Output parameters The output can be configured in the Settings-Modules-Ekip Signalling 1K-Output menu:
Parameter Description Default
Event which activates the output and switches the contacts.
Different protection proposals, statuses and thresholds are
Signal source available on the display; the Custom mode can be configured via None
Ekip Connect so as to extend the solutions and combine several
events
Minimum duration of the presence of the source before the
output is activated; the delay is given in seconds and can be set
within range: 0 s to 100 s, in 0.01 s steps
NOTES:
Delay 0 s
• the output will not be switched if the source is deactivated
before this time has elapsed
• if delay = 0 s the source must still be present for longer
than 300 µS
Defines the rest status of the contact with source not present
Contact Type NO
between: open (NO) and closed (NC)
Allows the output (and relative status led) to be kept activated
Latched (1) Off
(On) or deactivated (Off) when the event disappears
Defines the minimum closing time of the contact following the
rapid presence of sources:
• Source duration < min. activation = contact is activated for the
min Activation
Time (2) minimum activation time 0 ms
Source duration ≥ min. activation = contact is activated for as
long as the source persists
Choose between: 0 ms, 100 ms, 200 ms
(1) deactivate the latchings of the outputs used if the Measurement module is used for the Power
Controller function
(2) if Measurement module is used for the Power Controller function, the Pulse Mode option will also
be available; if selected, the output is kept activated for a set time that depends on the function,
regardless of whether the event that activated it persists
About The About-Modules menu contains the specific menu of the module, in which the statuses of the input
(On/Off) and output (Open/Closed) are present.
Test The output test command can be executed in the Test menu (page 125).
203 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 Internal accessories | 9 - Ekip Maintenance