Page 71 - MCCB-XT5
P. 71

ABB | SACE Tmax XT

       9 - Motor protections



                               List The Motor Protection package, available by default and only for Ekip M Touch, comprises protections:
                                     Name           Type of protection              Page
                                     R JAM          Motor block (post startup)      70
                                     R STALL        Motor block (always activated)  70
                                     UC             Under-current                   71
                                     U              Phase loss                      71
                                     PTC            Maximum temperature             72

                                    The Motor protections conform to standard IEC 60947-4-1 and relative annex 2.



           Trip class and parameters The trip class mentioned in standard IEC 60947-4-1 is available in Trip units with Motor Class parameter
                                    (page 121).
                                    Its value establishes:
                                     •  the trip time of L protection (Time t1)
                                     •  the start-up time (Motor start-up), calculated from the moment that at least one phase exceeds
                                       the fixed threshold of 0.25 x I1, during which some protections are inhibited
                                     •  the thermal memory L reset time after a TRIP (tmem res)
                                     Motor Class        t1 (s)              Motor start-up (s)  tmem res (min)
                                     5E                 12                  3                  5
                                     10E                22                  5                  10
                                     20E                45                  10                 20
                                     30E                72                  20                 33
























                                    Figure 31

                                           NOTE: temporary switch-off during Motor Startup-up is valid and activated for protections
                                           G, R Jam and U if enabled; if the protections are disabled they remain off before and after
                                           Motor Start-up.


                        Thresholds Unlike the other current protections, the R Stall, R Jam and UC thresholds are not related to In, but to
                                    threshold I1 (L protection), given as Ir in the respective configuration menus;
                                    Example
                                    Rating plug = 400 A, Threshold I1 = 0.8 In (--> 320 A); Threshold Ij = 2.5 Ir (--> 2.5 x 320 A = 800 A)












       69 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                                 Protections | 9 - Motor protections