Page 71 - MCCB-XT5
P. 71
ABB | SACE Tmax XT
9 - Motor protections
List The Motor Protection package, available by default and only for Ekip M Touch, comprises protections:
Name Type of protection Page
R JAM Motor block (post startup) 70
R STALL Motor block (always activated) 70
UC Under-current 71
U Phase loss 71
PTC Maximum temperature 72
The Motor protections conform to standard IEC 60947-4-1 and relative annex 2.
Trip class and parameters The trip class mentioned in standard IEC 60947-4-1 is available in Trip units with Motor Class parameter
(page 121).
Its value establishes:
• the trip time of L protection (Time t1)
• the start-up time (Motor start-up), calculated from the moment that at least one phase exceeds
the fixed threshold of 0.25 x I1, during which some protections are inhibited
• the thermal memory L reset time after a TRIP (tmem res)
Motor Class t1 (s) Motor start-up (s) tmem res (min)
5E 12 3 5
10E 22 5 10
20E 45 10 20
30E 72 20 33
Figure 31
NOTE: temporary switch-off during Motor Startup-up is valid and activated for protections
G, R Jam and U if enabled; if the protections are disabled they remain off before and after
Motor Start-up.
Thresholds Unlike the other current protections, the R Stall, R Jam and UC thresholds are not related to In, but to
threshold I1 (L protection), given as Ir in the respective configuration menus;
Example
Rating plug = 400 A, Threshold I1 = 0.8 In (--> 320 A); Threshold Ij = 2.5 Ir (--> 2.5 x 320 A = 800 A)
69 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 Protections | 9 - Motor protections