                   Protection R JAM Function
                                    R Jam is a protection against motor block: if the current of one or more phases exceeds threshold Ij for
                                    longer than time tj, the protection activates and sends a TRIP command.
                                    The R Jam protection is inhibited during Motor start-up.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  the summary table of the protections with the calculation formulas (page 83)
                                     •  the graph with trip curve (page 98)
                                    Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                                  Establishes the value that activates the protection.
                                                  The value is given as both absolute value (amperes) and relative
                                     Threshold Ij                                                     1,0 Ir
                                                  value (Ir) and can be set within the range: 1 Ir to 10 Ir in 0.1 Ir
                                                  steps
                                                  This is the trip time of the protection; the value is given in
                                     Time tj                                                          2 s
                                                  seconds and can be set within a range: 2 s to 10 s, in 0.5 s steps
                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 76).



                 Protection R STALL Function
                                    R Stall protects against motor block, but unlike R Jam, it is not inhibited during Motor startup-up: if the
                                    current of one or more phases exceeds threshold Ir for longer than time tr, the protection activates and
                                    sends a TRIP command.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  the summary table of the protections with the calculation formulas (page 83)
                                     •  the graph with trip curve (page 99)
                                    Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                                  Establishes the value that activates the protection.
                                                  The value is given as both absolute value (amperes) and relative
                                     Threshold Is                                                     2,0 Ir
                                                  value (Ir) and can be set within the range: 2 Ir to 10 Ir in 0.1 Ir
                                                  steps
                                                  This is the trip time of the protection; the value is given in
                                     Time ts                                                          1 s
                                                  seconds and can be set within a range: 1 s to 10 s, in 0.5 s steps
                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 76).