ABB | SACE Tmax XT

                      Protection UC Function
                                    UC protects the motor in reduced or no load conditions: the protection sends a TRIP command if all the
                                    current values detected by the unit drop below threshold luc for longer than time tuc.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 83)
                                     •  the graph with trip curve (page 99)
                                    Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                                  Establishes the value that activates the protection.
                                                  The value is given as both absolute value (amperes) and relative
                                     Threshold Iuc                                                    0,5 Ir
                                                  value (Ir) and can be set within the range: 0.5 Ir to 0.9 Ir in 0.1 Ir
                                                  steps
                                                  This is the trip time of the protection; the value is given in
                                     Time Iuc                                                         1 s
                                                  seconds and can be set within a range: 1 s to 20 s, in 0.5 s steps
                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 76).



                       Protection U Function
                                    U protects the motor in the event of phase loss: the protection sends a TRIP command if the rms value
                                    of at least one phase drops below the 0.1 In threshold and, at the same time, a current exceeds 0.25 for
                                    longer than time tu; the protection is inhibited during Motor start-up.
                                    If an alarm due to U protection occurs during Motor start-up, the trip unit calculates the trip time of the
                                    protection using whichever is the lowest value between: tu and half of Motor start-up
                                           IMPORTANT: in this case, if the alarm occurs on start-up and the calculated TRIP time is
                                           sufficiently long to last even until the Motor start-up window closes, the trip unit still
                                           considers the previously calculated minimum value as TRIP time

                                    To check and simulate the trip times in relation to all the parameters, please consult the summary table of
                                    the protections with the operating characteristics (page 83)
                                    Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                                  This is the trip time of the protection; the value is given in
                                     Time tu                                                          1 s
                                                  seconds and can be set within a range: 1 s to 10 s, in 0.5 s steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 76).


















       71 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                                 Protections | 9 - Motor protections