Page 134 - B_ELSB_Cat_2022_01_MCBs
P. 134

1/134            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Coordination tables: selectivity




                          E.    S800N
                Char.           C
          L.         Icu        36
                     [kA]  In [A]  25     32        40        50        63        80        100       125
                          6               0.4       0.5       0.7       0.9       1.4       2.4       4.8
                          10              0.3       0.4       0.5       0.7       0.9       1.3       2
                          13              0.3       0.4       0.5       0.7       0.9       1.3       1.9
                          16              0.3       0.4       0.5       0.7       0.9       1.3       1.9
                          20                        0.4       0.5       0.7       0.9       1.2       1.8
          S200M  B   15
                          25                        0.4       0.5       0.7       0.9       1.2       1.8
                          32                                  0.5       0.6       0.8       1         1.4
                          40                                            0.6       0.8       1         1.4
                          50                                                      0.7       0.9       1.3
                          63                                                                0.9       1.2

                          E.    S800N
                Char.           C
          L.         Icu        36
                     [kA]
                          In [A]  25      32        40        50        63        80        100       125
                          0.5   T         T         T         T         T         T         T         T
                          1     T         T         T         T         T         T         T         T
                          1.6   0.6       T         T         T         T         T         T         T
                          2     0.5       1         T         T         T         T         T         T
                          3     0.3       0.5       0.7       1.2       2.1       6.4       T         T
                          4     0.3       0.4       0.7       1         1.5       2.6       6.1       T
                          6               0.4       0.5       0.7       0.9       1.4       2.4       4.8
                          8               0.3       0.4       0.5       0.7       0.9       1.3       2
          S200M  C   15   10              0.3       0.4       0.5       0.7       0.9       1.3       2
                          13              0.3       0.4       0.5       0.7       0.9       1.3       1.9
                           16             0.3       0.4       0.5       0.7       0.9       1.3       1.9
                           20                       0.4       0.5       0.7       0.9       1.2       1.8
                           25                       0.4       0.5       0.7       0.9       1.2       1.8
                           32                                 0.5       0.6       0.8       1         1.4
                           40                                           0.6       0.8       1         1.4
                           50                                                     0.7       0.9       1.3
                           63                                                               0.9       1.2





















          E. = feed side
          L. = load side
          T  = Total selectivity up to breaking capacity of the switch on load side
              Selectivity limit values indicated in kA
   129   130   131   132   133   134   135   136   137   138   139