Page 136 - B_ELSB_Cat_2022_01_MCBs
P. 136

1/136            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Coordination tables: selectivity




                          E.   S800N
                Char.          D
          L.         Icu       36
                     [kA]  In [A]  25    32        40        50        63         80        100       125
                          6    0.5       1         1.2       2         2.8        T         T         T
                          10   0.4       0.6       0.8       1.1       1.4        2.8       3.9       7.4
                          13   0.4       0.6       0.8       1.1       1.4        2.5       3.3       5.6
                          16             0.6       0.8       1.1       1.4        2.5       3.3       5.6
                          20                       0.8       1.1       1.3        2.3       3         4.7
          S200M B    15
                          25                       0.8       1.1       1.3        2.3       3         4.7
                          32                                 0.9       1.1        1.9       2.4       3.7
                          40                                           1.1        1.9       2.4       3.7
                          50                                                      1.5       1.9       2.3
                          63                                                                1.7       2.3

                          E.   S800N
                Char.          D
          L.         Icu       36
                     [kA]
                          In [A]  25     32        40        50        63         80        100       125
                          0.5  T         T         T         T         T          T         T         T
                          1    T         T         T         T         T          T         T         T
                          1.6  T         T         T         T         T          T         T         T
                          2    T         T         T         T         T          T         T         T
                          3    0.7       2.2       4.4       T         T          T         T         T
                          4    0.7       1.3       2.2       4.4       7.7        T         T         T
                          6    0.5       1         1.2       2         2.8        T         T         T
                          8    0.4       0.6       0.8       1.1       1.4        2.8       3.9       7.4
          S200M C    15   10   0.4       0.6       0.8       1.1       1.4        2.8       3.9       7.4
                          13   0.4       0.6       0.8       1.1       1.4        2.5       3.3       5.6
                          16             0.6       0.8       1.1       1.4        2.5       3.3       5.6
                          20                       0.8       1.1       1.3        2.3       3         4.7
                          25                       0.8       1.1       1.3        2.3       3         4.7
                          32                                 0.9       1.1        1.9       2.4       3.7
                          40                                           1.1        1.9       2.4       3.7
                          50                                                      1.5       1.9       2.3
                          63                                                                1.7       2.3





















          E. = feed side
          L. = load side
          T  = Total selectivity up to breaking capacity of the switch on load side
              Selectivity limit values indicated in kA