Page 135 - B_ELSB_Cat_2022_01_MCBs
P. 135

1
                                                                                                            1/135



          —
          MCBs technical details
          Coordination tables: selectivity




                          E.    S800N
                Char.           C
          L.         Icu        36
                     [kA]  In [A]  25     32        40        50        63        80        100       125
                          0.5   T         T         T         T         T         T         T         T
                          1     2.1       T         T         T         T         T         T         T
                          1.6   0.8       2.3       T         T         T         T         T         T
                          2     0.4       0.7       2.3       T         T         T         T         T
                          3     0.3       0.5       0.7       1.2       2.2       6.4       T         T
                          4     0.3       0.4       0.7       1         1.4       2.6       6.2       T
                          6               0.4       0.6       0.8       1.1       1.8       3.2       6.4
                          8                         0.5       0.7       0.9       1.2       1.8       2.8
          S200M  D   15   10                                  0.7       0.9       1.2       1.8       2.8
                          13                                            0.7       1         1.4       2
                          16                                                      1         1.4       2
                          20                                                                1         1.4
                          25                                                                          1.4
                          32
                          40
                          50
                          63

                          E.    S800N
                Char.           C
          L.         Icu        36
                     [kA]  In [A]  25     32        40        50        63        80        100       125
                          0.5   T         T         T         T         T         T         T         T
                          1     2.1       T         T         T         T         T         T         T
                          1.6   0.8       2.3       T         T         T         T         T         T
                          2     0.4       0.7       2.3       T         T         T         T         T
                          3     0.3       0.5       0.7       1.2       2.2       6.4       T         T
                          4     0.3       0.4       0.7       1         1.4       2.6       6.2       T
                          6               0.4       0.6       0.8       1.1       1.8       3.2       6.4
                          8                         0.5       0.7       0.9       1.2       1.8       2.8
          S200M  K   15   10                                  0.7       0.9       1.2       1.8       2.8
                          13                                            0.7       1         1.4       2
                          16                                                      1         1.4       2
                          20                                                                1         1.4
                          25                                                                          1.4
                          32
                          40
                          50
                          63










         E. = feed side
         L. = load side
         T  = Total selectivity up to breaking capacity of the switch on load side
             Selectivity limit values indicated in kA
   130   131   132   133   134   135   136   137   138   139   140