Page 174 - B_ELSB_Cat_2022_01_MCBs
P. 174
1/174 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
TmaxXT - S300P @ 415V AC
Supply s. XT1
Char. Version B, C, N, S, H
Relay TM
Iu [A] 160
Load s. Icu [kA] 18, 25, 36, 50, 70
In [A] 16 20 25 32 40 50 63 80 100 125 160
0,2...4 T T T T T T T T T T T
6 5.5 5.5 5.5 5 5 5 10 T T T T
8 5.5 5.5 5.5 5.5 5 10 10 T T T
10 2 2 3 3 5 8.5 15 T T
13 2 2 3 6 7.5 13.5 T
16 2 2 3 6 7.5 13.5 T
S300P D,K 25
20 2 3 6 6 11 T
25 3 6 6 10 T
32 4 6 9.5 15
40 8 15
50 5 10
63 10
TmaxXT - S300P @ 415V AC
Supply s. XT2
Char. Version N, S, H, L, V
Relay TM
Iu [A] 160
Load s. Icu [kA] 36, 50, 70, 120, 150
In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160
0,2...4 T25 T25 T25 T25 T25 T25 T25 T25 T25 T25 T25 T25
6 5.5 5.5 5.5 5.5 5.5 5.5 5.5 10 T25 T25 T25 T25
8 5.5 5.5 5.5 5.5 5.5 10 10 T25 T25 T25
10 3 3 3 4.5 5 8.5 15 T25 T25
13 3 3 4.5 3 6 7.5 13.5 T25
16 3 4.5 3 6 7.5 13.5 T25
S300P D,K 25
20 3 3 6 6 11 T25
25 3 6 6 10 T25
32 4 6 9.5 15
40 8 15
50 5 10
63 10
TmaxXT - S300P @ 415V AC
Supply s. XT3
Char. Version N, S
Relay TM
Iu [A] 250
Load s. Icu [kA] 36, 50
In [A] 63 80 100 125 160 200 250
0,2...4 T25 T25 T25 T25 T25 T25 T25
6 10 T25 T25 T25 T25 T25 T25
8 10 10 T25 T25 T25 T25 T25
10 5 7.5 15 T25 T25 T25 T25
13 3 6 7.5 13.5 T25 T25 T25
16 3 6 7.5 13.5 T25 T25 T25
S300P D,K 25
20 3 6 6 11 T25 T25 T25
25 3 6 6 10 T25 T25 T25
32 4 6 9.5 15 15 15
40 8 15 15 15
50 5 10 15 15
63 10 15 15