Page 185 - B_ELSB_Cat_2022_01_MCBs
P. 185

1
                                                                                                            1/185



          —
          MCBs technical details
          Coordination tables: selectivity




          Short-circuit discrimination (in kA) apply for combinations : fuse gL / gG – S 750 DR – S 200 P
                                                          1)





                       fuse:             63 A gG                 80 A gG                     100 A gG
                     supply side:                                     S 750 DR
                 Char.                                                 E / K
          final        I [kA]                                          25
          circuit:     cu
                             I  [A]  32  40   50    63   32   40   50    63   80   32   40   50    63   80  100
                              n
                               ≤ 2  15   15    15   15   25   25   25    25   25   25   25   25    25   25   25
                                3   10   10    10   10   25   25   15    15   25   25   25   25    25   25   25
                                4   10   10    10   10   20   20   15    15   15   25   25   25    25   25   25
                                6   10   10    10   10   17   16   15    14   14   25   25   20    20   20   20
                        25      8    7    6    6     5   10   10   10    8     7   20   20    15   15   15   14
                               10    7    6    6     5   10   10   10    8     7   20   15    15   15   15   14
                  B, C,        13    6    6    6     5    9    8    8    7     6   15   15    15   15   15   14
          S 200 P
                  D, K, Z      16    6    6    6     5    9    8    8     7    6   12   12    10   10    9    8
                               20    5    5   4.5  4.5    6    7    7   6.5  5.5   12   12    10   10    9    8
                               25        4.5  4.5    4         7    6     6  5.5        10    10   10    9    8
                               32              4   3.5              6   5.5    5              10   10    8    7
                         15    40                    3                    5    4                    9    7    6
                               50                                              2                         5    4
                               63                                                                             4
                                               2
                                                                                    2
          1)  The selectivity limit current I  results from the let-through I t-value of S 750 DR plus S 200 P and the pre-arcing (melting) I t-value of a fuse acc. to IEC / EN 60269
                            s1
          Short-circuit discrimination (in kA) apply for combinations : fuse gL / gG – S 750 DR – S 200 P
                                                          1)





                       fuse:                      125 A gG                               160 A gG
                     supply side:                                     S 750 DR
                 Char.                                                 E / K
          final
          circuit:     I [kA]                                          25
                       cu
                             I  [A]  32     40    50     63    80    100     32    40     50    63     80    100
                              n
                               ≤ 2   25     25    25     25    25     25     25    25     25    25     25    25
                                3    25     25    25     25    25     25     25    25     25    25     25    25
                                4    25     25    25     25    25     25     25    25     25    25     25    25
                                6    25     25    25     25    25     25     25    25     25    25     25    25
                        25      8    25     25    25     25    25     25     25    25     25    25     25    25
                               10    25     25    25     25    25     20     25    25     25    25     25    25
                  B, C,        13    22     22    20     20    20     18     22    22     20    20     25    25
          S 200 P
                  D, K, Z      16    22     22    20     18    18     15     22    22     20    18     25    25
                               20    20     20    20     18    18     15     20    20     20    18     25    25
                               25           15    15     15    15     12           15     15    15     15    15
                               32                 15     15    15     12                  15    15     15    15
                         15    40                        15     12    10                        15     15    15
                               50                               10    10                               15    15
                               63                                      9                                     15
          1)  The selectivity limit current I  results from the let-through I t-value of S 750 DR plus S 200 P and the pre-arcing (melting) I t-value of a fuse acc. to IEC / EN 60269
                                               2
                                                                                    2
                            s1
   180   181   182   183   184   185   186   187   188   189   190