Coordination tables: selectivity
Short-circuit discrimination (in kA) apply for combinations : fuse gL / gG – S 750 DR – S 200 P
1)
fuse: 63 A gG 80 A gG 100 A gG
supply side: S 750 DR
Char. E / K
final I [kA] 25
circuit: cu
I [A] 32 40 50 63 32 40 50 63 80 32 40 50 63 80 100
n
≤ 2 15 15 15 15 25 25 25 25 25 25 25 25 25 25 25
3 10 10 10 10 25 25 15 15 25 25 25 25 25 25 25
4 10 10 10 10 20 20 15 15 15 25 25 25 25 25 25
6 10 10 10 10 17 16 15 14 14 25 25 20 20 20 20
25 8 7 6 6 5 10 10 10 8 7 20 20 15 15 15 14
10 7 6 6 5 10 10 10 8 7 20 15 15 15 15 14
B, C, 13 6 6 6 5 9 8 8 7 6 15 15 15 15 15 14
S 200 P
D, K, Z 16 6 6 6 5 9 8 8 7 6 12 12 10 10 9 8
20 5 5 4.5 4.5 6 7 7 6.5 5.5 12 12 10 10 9 8
25 4.5 4.5 4 7 6 6 5.5 10 10 10 9 8
32 4 3.5 6 5.5 5 10 10 8 7
15 40 3 5 4 9 7 6
50 2 5 4
63 4
2
2
1) The selectivity limit current I results from the let-through I t-value of S 750 DR plus S 200 P and the pre-arcing (melting) I t-value of a fuse acc. to IEC / EN 60269
s1
Short-circuit discrimination (in kA) apply for combinations : fuse gL / gG – S 750 DR – S 200 P
1)
fuse: 125 A gG 160 A gG
supply side: S 750 DR
Char. E / K
final
circuit: I [kA] 25
cu
I [A] 32 40 50 63 80 100 32 40 50 63 80 100
n
≤ 2 25 25 25 25 25 25 25 25 25 25 25 25
3 25 25 25 25 25 25 25 25 25 25 25 25
4 25 25 25 25 25 25 25 25 25 25 25 25
6 25 25 25 25 25 25 25 25 25 25 25 25
25 8 25 25 25 25 25 25 25 25 25 25 25 25
10 25 25 25 25 25 20 25 25 25 25 25 25
B, C, 13 22 22 20 20 20 18 22 22 20 20 25 25
S 200 P
D, K, Z 16 22 22 20 18 18 15 22 22 20 18 25 25
20 20 20 20 18 18 15 20 20 20 18 25 25
25 15 15 15 15 12 15 15 15 15 15
32 15 15 15 12 15 15 15 15
15 40 15 12 10 15 15 15
50 10 10 15 15
63 9 15
1) The selectivity limit current I results from the let-through I t-value of S 750 DR plus S 200 P and the pre-arcing (melting) I t-value of a fuse acc. to IEC / EN 60269
2
2
s1