Page 180 - B_ELSB_Cat_2022_01_MCBs
P. 180

1/180            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Coordination tables: selectivity




          Discrimination of S750 DR with respect to downstream MCB S200M / S400M compared to fuse protection
          MCBs
                                                                                               S 200
                                                                                               S 200 M
                    supply side:     S 750 DR                               fuse
          final     Char.            E / K                                  gG
          circuit:
                          I [kA]     25
                          cu
                                 I  [A]  16  20  25  32  40  50  63  80  100  16  20  25  35  40  50  63  80 100
                                 n
          S200M     Z     10      ≤ 2  15  15  15  15  15  15  15  15  15    0.5  2   10  10  15  15  15  15  15
          S400M
                                   3  15  15  15  15  15  15  15  15  15     0.3  0.7  1.8  6  15  15  15  15  15
                                   4  15  15  15  15  15  15  15  15  15     0.3  0.6  1.3  3.5  4  7  15  15  15
                                   6  15  15  15  15  15  15  15  15  15     0.2  0.5  0.9  1.3  2.7  3.8  6  15  15
                                   8  15  15  15  15  15  15  15  15  15         0.4  0.6  1.3  1.5  2.4  4  6  6
                                  10  15  15  15  15  15  15  15  15  15         0.4  0.6  1.3  1.5  2.4  4  6  6
                                  16      15  15  15  15  15  15  15  15             0.5  1.1  1.5  1.7  3  4.5  6
                                  20          15  15  15  15  15  15  15                     0.7  1.4  2  3  4.4
                                  25              15  15  15  15  15  15                     0.7  1.4  2  3  4.4
                                  32                  15  15  15  15  15                              2   3   4
                                  40                      15  15  15  15                              2   3   4
                                  50                          15  15  15                                      3
                                  63                              15  15                                      3

                          Limited overload selectivity
   175   176   177   178   179   180   181   182   183   184   185