          Coordination tables: selectivity




          Short-circuit discrimination (in kA) apply for combinations : fuse gL / gG – S 750 DR – S 200 / S 400 E
                                                          1)





                       fuse:             63 A gG                 80 A gG                     100 A gG
                     supply side:                                     S 750 DR
                 Char.                                                 E / K
          final        I [kA]                                          25
          circuit:     cu
                             I  [A]  32  40   50    63   32   40   50    63   80   32   40   50    63   80  100
                              n
                               ≤ 2  15   15    15   15   15   15   15    15   15   15   15   15    15   15   15
                                3   10   10    10   10   10   10   10    10   10   10   10    10   10   10   10
                                4   10   10    10   10   10   10   10    10   10   10   10    10   10   10   10
                                6   10   10    10   10   10   10   10    10   10   10   10    10   10   10   10
                                8    7    6    6     5   10   10   10    8     7   10   10    10   10   10   10
                               10    7    6    6     5   10   10   10    8     7   10   10    10   10   10   10
          S 200   B, C,   6    13    6    6    6     5    9    8    8     7    6   10   10    10   10   10   10
          S 400 E  D, K, Z     16    6    6    6     5    9    8    8     7    6   10   10    10   10    9    8
                               20    5    5   4.5  4.5    6    7    7   6.5   5.5  10   10    10   10    9    8
                               25        4.5  4.5    4         7    6     6   5.5       10    10   10    9    8
                               32              4   3.5              6   5.5    5              9     9    8    7
                               40                    3                    5    4                    8    7    6
                               50                                              2                         5    4
                               63                                                                             4

                                               2
          1)  The selectivity limit current I  results from the let-through I t-value of S 750 DR plus S 200 /S 400 and the pre-arcing (melting) I t-value of a fuse acc. to IEC / EN 60269
                                                                                       2
                            s1
          Short-circuit discrimination (in kA) apply for combinations : fuse gL / gG – S 750 DR – S 200 / S 400 E
                                                          1)




                       fuse:                      125 A gG                               160 A gG
                     supply side:                                     S 750 DR
                 Char.                                                 E / K
          final
          circuit:     I [kA]                                          25
                       cu
                             I  [A]  32     40    50     63    80    100     32    40     50    63     80    100
                              n
                               ≤ 2   15     15    15     15    15     15     15    15     15    15     15    15
                                3    10     10    10     10    10     10     10    10     10    10     10    10
                                4    10     10    10     10    10     10     10    10     10    10     10    10
                                6    10     10    10     10    10     10     10    10     10    10     10    10
                                8    10     10    10     10    10     10     10    10     10    10     10    10
                               10    10     10    10     10    10     10     10    10     10    10     10    10
          S 200   B, C,        13    10     10    10     10    10     10     10    10     10    10     10    10
          S 400 E  D, K, Z  6  16    10     10    10     10    10     10     10    10     10    10     10    10
                               20    10     10    10     10    10     10     10    10     10    10     10    10
                               25           10    10     10    10     10           10     10    10     10    10
                               32                 10     10    10     10                  10    10     10    10
                               40                        10    10     10                        10     10    10
                               50                              10     10                               10    10
                               63                                      9                                     10
                                                                                       2
          1)  The selectivity limit current I  results from the let-through I t-value of S 750 DR plus S 200 /S 400 and the pre-arcing (melting) I t-value of a fuse acc. to IEC / EN 60269
                                               2

                            s1