          MCBs technical details
          Coordination tables: selectivity




          Discrimination of S750 DR with respect to downstream MCB S200P compared to fuse protection
          MCBs
                                                                                               S 200 /
                                                                                               S 400
                    supply side:     S 750 DR                               fuse
          final     Char.            E / K                                  gG
          circuit:
                          I [kA]     25
                          cu
                                 I  [A]  16  20  25  32  40  50  63  80  100  16  20  25  35  40  50  63  80 100
                                 n
          S200P     B     25       6  25  25  25  25  25  25  25  25  25     0.2  0.4  0.6  1.3  2.5  3  5.5  12  25
                                  10  25  25  25  25  25  25  25  25  25             0.6  1  1.5  1.8  2.5  3.7  5.5
                                  13  25  25  25  25  25  25  25  25  25             0.6  1  1.5  1.8  2.5  3.7  5.5
                                  16      25  25  25  25  25  25  25  25                  1  1.4  1.6  2  3   5
                                  20          25  25  25  25  25  25  25                     0.7  1.5  2  3   4
                                  25              25  25  25  25  25  25                     0.7  1.5  2  3   4
                          15      32                  15  15  15  15  15                             1.9  2.7  3.5
                                  40                      15  15  15  15                             1.9  2.7  3.5
                                  50                          15  15  15                                 2.7  3.4
                                  63                              15  15                                 2.7  3.4

                          Limited overload selectivity


          Discrimination of S750 DR with respect to downstream MCB S200P compared to fuse protection
          MCBs
                                                                                               S 200 /
                                                                                               S 400
                    supply side:     S 750 DR                               fuse
          final     Char.            E / K                                  gG
          circuit:
                          I [kA]     25
                          cu
                                 I  [A]  16  20  25  32  40  50  63  80  100  16  20  25  35  40  50  63  80 100
                                 n
          S200P     C     25      ≤ 2  25  25  25  25  25  25  25  25  25    0.3  0.8  1.5  6  10  25  25  25  25
                                   3  25  25  25  25  25  25  25  25  25     0.3  0.8  1.5  6  10  25  25  25  25
                                   4  25  25  25  25  25  25  25  25  25     0.3  0.6  1  3.3  4  6  25  25  25
                                   6  25  25  25  25  25  25  25  25  25     0.2  0.4  0.6  1.3  2.5  3  5.5  12  25
                                   8  25  25  25  25  25  25  25  25  25             0.6  1  1.5  1.8  2.5  3.7  5.5
                                  10  25  25  25  25  25  25  25  25  25             0.6  1  1.5  1.8  2.5  3.7  5.5
                                  13  25  25  25  25  25  25  25  25  25             0.6  1  1.5  1.8  2.5  3.7  5.5
                                  16      25  25  25  25  25  25  25  25                  1  1.4  1.6  2  3   5
                                  20          25  25  25  25  25  25  25                     0.7  1.5  2  3   4
                                  25              25  25  25  25  25  25                     0.7  1.5  2  3   4
                          15      32                  15  15  15  15  15                             1.9  2.7  3.5
                                  40                      15  15  15  15                             1.9  2.7  3.5
                                  50                          15  15  15                                 2.7  3.4
                                  63                              15  15                                 2.7  3.4
                          Limited overload selectivity