1/208            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          S 200 MUC series AC/DC Applications




          UC = Universal Current = AC/DC                      it is therefore necessary to take into account the polarity
          S 200 MUC MCBs can be used in the one-pole version   during the installation process.
          as 220 V DC, and in the 2-pole or 4-pole version with   Doing so ensures that in the case of a short circuit the
          series connection of two poles up to 440 V DC.      magnetic field of the permanent magnets corresponds
          S 200 MUC contains fitted permanent magnets, which   with the electromagnetic field of the short-circuit current,
          assists in the forced extinguishing of the arc.     therefore safely leading the short circuit into the arc chute.
          If voltages to earth exceeding  220 V DC may occur,   Incorrect polarities may cause damage to the MCB. This is
          2-pole S 200 MUC is to be used for one-pole disconnection,   why – in the case of top-fed devices – terminal 1 must be
          and four-pole S 200 MUC for all-pole disconnection.  connected to (-) and terminal to 3 (+).
          For DC incoming supply from above S 200 MUC-… MCBs   Example for permissible voltages between the conductors
          have, in the area of arc chutes, permanent magnets,   depending on the number of poles and circuit layout:



          voltage between conductors  U n  220 V–  440 V–  440 V–      440 V–         440 V– (voltage reversal)
          voltage between        U n  220 V–    220 V–     440 V–      220 V–         220 V–
          conductor and earth
          MCB                        1-pole     2-pole     2-pole      2-pole         4-pole
                                     S 201 MUC  S 202 MUC  S 202 MUC   S 202 MUC      S 204 MUC
          supply from below











          supply from above













          Examples for different voltage levels betweeen conductor and earth in the case of identical voltage between conductors:
          voltage between conductors  U  440 V– all-pole disconnection  440 V– 1-pole disconnection  440 V– all pole disconnection
                                  n
          voltage between        U n  220 V– circuit symmetrically   440 V– circuit unsymmetrically   440 V– circuit unearthed or
          conductor and earth        earthed                  earthed                  unsymmetrically earthed
          MCB                        2-pole                   2-pole                   4-pole
                                     S 202 MUC                S 202 MUC                S 204 MUC















          ➀ in the circuit diagram, the negative pole is earthed.   ➁ in the circuit diagram, the positive pole is earthed.