          MCBs technical details
          Use of MCBs in direct current circuits




          Use of S 200/S 200 M/S 200 P miniature circuit-breakers    consideration, the outgoing circuit may be implemented
          in direct current circuits 72 VDC/125 VDC           from above or below the device.
          In DC systems up to 72 VDC or, as the case may be, series   For higher direct voltage up to 440 VDC devices of the S 280
          connection up to 125 VDC, customary S 200/S 200 M series   UC series must be used.
          MCBs can be used.Polarity does not need to be taken into




          Example for max. permissible voltages between conductors depending on the number
          of poles and type of connection.






                                        SK 0173 Z 99








          Examples for different voltages between a conductor and earth where voltages between
          conductors are identical: