          MCBs technical details
          Instruction for use of S 200 S




          Connection and disconnection of different types of cables   Disconnection of cables
          on the load side
          Type of cables and cross sections













                                                              The cables may only be removed after operating the termi-
                                                              nal’s opening mchanism.
          Connection of cables                                •  If one cable is removed, the correct position of the remain-
                                                               ing cable must be checked.















          •  Connection of one cable per opening.
          •  Rigid and flexible cables with end sleeves may be directly
           connected.
          •  If flexible cables without end sleeves are to be connected,
           the terminal
           must be opened. Splicing of the wires must be avoided.
          •  The cable must be inserted into the terminal either as far
           as possible
           or in such a way that a sufficient connection is obvious.
          •  The tightness of the connection must be checked.






          Processing instructions                             Wire stripping length / size of end sleeves for all cables
          The screwless terminal at the load side of the S 200 S    Wire stripping length and end sleeve length 12 (+2) mm
          is designed so that copper cables basically may be
          connected without further preparation. If end sleeves are   Distribution boards with metal cover
          used as splicing protection for flexible cables, the   The distance from a metallic cover to the “shoulder”
          compression                                         of the miniature circuit breaker must be at least 6 mm
          of the end sleeves must comply with the pull-out forces in   on the load side due to the arrangement of the easiliy
          accordance with standard IEC/EN 60898-1 table J.3.  accessible measurement point.

          Recommended tools for flexible cables with end sleeves
          Crimp tool with trapezoid compression profile