1/206            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          S 200 UDC series DC Applications




          DC = Direct Current                                 For DC incoming supply from above S 200 UDC-… MCBs
          S 200 UDC MCBs can be used in the one-pole version as    have, in the area of arc chutes, permanent magnets, it is
          60 V DC (125 V DC up to 40 A), and in the 2-pole version with   therefore necessary to take into account the polarity during
          series connection of two poles up to 125 V DC (250 V DC up   the installation process.
          to 40 A).                                           Doing so ensures that in the case of a short circuit the
                                                              magnetic field of the permanent magnets corresponds
          S 200 UDC contains fitted permanent magnets, which    with the electromagnetic field of the short-circuit current,
          assists in the forced extinguishing of the arc.     therefore safely leading the short circuit into the arc chute.
          If voltages to earth exceeding 60 V DC may occur, 2-pole S   Incorrect polarities may cause damage to the MCB. This is
          200 UDC is to be used for one-pole disconnection.   why – in the case of top-fed devices – terminal 1 must be
                                                              connected to (-) and terminal to 3 (+).





          Example for permissible voltages between the conductors depending on the number of poles and circuit layout:
          voltage        U n  60 V DC            125 V DC              125 V DC             125 V DC
          between            (125 V DC up to 40 A)  (250 V DC up to 40 A)  (250 V DC up to 40 A)  (250 V DC up to 40 A)
          conductors
          voltage        U n  60 V DC            60 V DC               125 V DC             60 V DC
          between            (125 V DC up to 40 A)  (125 V DC up to 40 A)  (250 V DC up to 40 A)  (125 V DC up to 40 A)
          conductor
          and earth
          MCB                1-pole              2-pole                2-pole               2-pole
                             S 201 UDC           S 202 UDC             S 202 UDC            S 202 UDC
          supply from below












          supply from above