Page 209 - B_ELSB_Cat_2022_01_MCBs
P. 209
1
1/209
—
MCBs technical details
S800 series DC applications
S800S-UC: The first choice as DC high performance MCB
The S800S-UC DC high performance MCB is in a wide range of DC applications at home.
Due to their high rated operational voltage of up to 1000 V DC the max. rated current of 125 A
and the high breaking capaicty of up to 50 kA, make these devices suitable for applications,
e.g.:
• DC track
• Galavanic applications
• Photovoltaics
S800S, N, and C: Up to 125 V DC on each pole
The AC range is also an interesting choice for DC applications up to 125 V DC per pole.
+ – + – + –
A B C
1 1 3 1 3 1 3
2 2 4 2 4
2 4
+ + –
D
+ – + – + –
E F G
1 3 5 1 3 1 3 5 7
2 4 6 2 4 2 4 6 8
S800S-UC
Short-circuit Contact to ground
Graphic between output terminals between output terminals and - earth
A 250 V DC 250 V DC
B 500 V DC 250 V DC
C 500 V DC 500 V DC
D 250 V DC 250 V DC
E 750 V DC 750 V DC
F 500 V DC 250 V DC (double failure)
G 750 V DC / 1000 V DC 500 V DC (double failure)
S800S, S800N, S800C
Short-circuit Contact to ground
Graphic between output terminals between output terminals and - earth
A 125 V DC 125 V DC
B 250 V DC 125 V DC
C 250 V DC 250 V DC
D 125 V DC 125 V DC
E 375 V DC 375 V DC
F 250 V DC 125 V DC (double failure)
G 500 V DC 125 V DC (double failure)