Page 214 - B_ELSB_Cat_2022_01_MCBs
P. 214

1/214            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Particular supply sources and loads




          Lighting circuit protection                         may be supplied directly by the device manufacturer.
          Selection of circuit-breakers for the protection of lighting   Considering the utilization current, it is important to select
          circuit and calculation of their rated current      the version of the breaker with a rated current just above
          To select the correct circuit-breaker for use in the protection   the value calculated, defining the cable cross-section
          of lighting circuits you need to know the type of load based   accordingly. The tables below show the rated current values
          on which you will work out the breaker’s rated current. The   of the circuit-breakers to be used according to the type
          protection circuit utilization current can be calculated simply   and power of the device connected.
          starting with the rated power and the lighting voltage, or it




          Table 1 High pressure discharge lamps
          230 V and 400 V AC three-phase with or without power factor correcting capacitors, star or delta connection

          Mercury vapour fluorescent lamp  Pw [W]  <700            <1000                  <2000
                                     I [A]   6                     10                     16
          Mercury vapour metal halogen lamp  Pw [W]  <375          <1000                  <2000
                                     I [A]   6                     10                     16
          High pressure sodium       Pw [W]  <400                                         <1000
          discharge lamp
                                     I [A]   6                                            16
          Table 2 Fluorescent lamps
          230 VAC single-phase/three-phase with neutral (400 V), with star connection.
          The tables indicate the rated current of the circuit-breakers according to the lamp power and type of power supply.

          Example of calculation
          - Starter dissipated power: 25% of lamp power
          - Reference temperature:   30 and 40 °C according to circuit-breaker
          - Power factor:      lamp without capacitors cos φ=0.6
                               lamp with capacitors cos φ=0.86
          Method of calculation
          -  IB = (PL * n°L * KST * KC) / (Un * cos φ)   where:   - Un     = rated voltage 230 V
                                                     - cos φ = power factor
                                                     - PL      = lamp power
                                                     - n°L    = number of lamps per phase
                                                     - KST   = 1.25
                                                     - KC    = 1 for star connection and 1.732
                                                               for delta connection


          Type of lamp  Tube diss. pwr. [W]  Number of lamps per phase
          Single     18             4    9     14   29    49   78    98   122   157  196   245  309   392  490
          without    36             2    4     7    14    24   39    49   61    78   98    122  154   196  245
          capacitors
                     58             1    3     4    9     15   24    30   38    48   60    76   95    121  152
          Single with   18          7    14    21   42    70   112   140  175   225  281   351  443   562  703
          capacitors  36            3    7     10   21    35   56    70   87    112  140   175  221   281  351
                     58             2    4     6    13    21   34    43   54    69   87    109  137   174  218
          Double with   2x18=36     3    7     10   21    35   56    70   87    112  140   175  221   281  351
          capacitors
                     2x36=72        1    3     5    10    17   28    35   43    56   70    87   110   140  175
                     2x58=116       1    2     3    6     10   17    21   27    34   43    54   68    87   109
          I  [A] - 2P and 4P circuit-breakers  1  2  3  6  10  16    20   25    32   40    50   63    80   100