          MCBs technical details
          S800 range features




                                    Play it safe: display the operational state
                                    The mechanical drive of the S800 high performance MCB is equipped with a trip-free
                                    release. It therefore switches independent of the actuating force or speed on the actuating
                                    lever.
                                    The trip position display thereby always reliably displays the exact position of the moving
                                      contact. The trip position provides additional trip detection allowing you to easily find the
                                    reason for the cut-off. Because the switch lever moves to the middle position in case
                                    of thermal or magnetic tripping, the user sees at a glance that this is an error state and can
                                    then initiate suitable measures.
                                    *Middle position of switch lever, see picture

                                    Reliable: the disconnector properties
                                    In OFF position (0 position), the S800 high performance MCB guarantees safe electrical
                                      isolation of the circuit compliant to IEC 60947-2.

                                    Flexible: the installation
                                    The S800 high performance MCB can be directly mounted onto any position on the DIN
                                    mounting rail without any impairment to its characteristics. Because the pole dimensions
                                    are identical for all rated currents, installation in switching systems is simplified.
                                    The S800 can be installed in different ways:
                                    •  together with other breakers in the same DIN rail horizontally or vertically
                                    •  as an individual breaker in a single fixed compartment where the breaker is switched on/
                                     off with a rotary handle from the door, and the breaker is mounted on the wall of the panel
                                    •  as an individual breaker in a single withdrawable module, when requirements for high
                                     availability in the installation are a must

                                    Cage and ring terminals
                                    When ordering you can choose between cage terminals or ring terminal connectors. No
                                      matter which type you select, both connection options  guarantee a high degree of reliability.
























                                    Doesn’t let go: the replaceable terminal adapter *
                                    The S800 standard equipment with interchangeable terminal adapter for wires, cables and
                                    rigid conductors guarantees a high level of flexibility and comfort. Fast and safe connection
                                    of the conductors is ensured by the “onboard terminal shutter” integrated into the body
                                    of the terminal, thereby preventing incorrect underclamping of the connections.