Page 218 - B_ELSB_Cat_2022_01_MCBs
P. 218

1/218            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Particular supply sources and loads




          wFor instance, a circuit-breaker with rated current 16 A, B   As regards the miniature circuit-breakers S200P series, two
          characteristic, with short-circuit rated capacity equal to 6 kA   different breaking capacities are indicated on the front side
                                                 2
          belongs to class 3 if it lets through max 35000 A s of specific   of the device, contained in a rectangle.
          energy.                                              The breaking capacity indicated above the operating
          The limiting class value (1, 2 or 3) is indicated on the front side   toggle is the one of the device, according to IEC/EN 60898
          of the device, within a square, in addition to the   standard, the breaking capacity indicated under the lever
          breaking capacity.                                   is regarding the limiting class which, according to the
                                                               standard, can be expressed only for values up to 10000 A.
   213   214   215   216   217   218   219   220   221   222   223