          MCBs technical details
          Particular supply sources and loads




          Single-phase transformer (primary voltage 230 V)-1P and 1P+N MCBs
          P  [kVA]                  I  [A]                   u  (%)                    Circuit-breaker on primary
           n                        n                         cc
                                                                                       side (1) and (2)
          0.1                       0.4                      13                        S 2* D1 o K1
          0.16                      0.7                      10.5                      S 2* D2 o K2
          0.25                      1.1                      9.5                       S 2* D3 o K3
          0.4                       1.7                      7.5                       S 2* D4 o K4
          0.63                      2.7                      7                         S 2* D6 o K6
          1                         4.2                      5.2                       S 2* D10 o K10
          1.6                       6.8                      4                         S 2* D16 o K16
          2                         8.4                      2.9                       S 2* D16 o K16
          2.5                       10.5                     3                         S 2* D20 o K20
          4                         16.9                     2.1                       S 2* D40 o K40
          5                         21.1                     4.5                       S 2* D50 o K50
          6.3                       27                       4.5                       S 2* D63 o K63

          Single-phase transformer (primary voltage 400 V)-2P MCBs
          P  [kVA]                  I  [A]                   u  (%)                    Circuit-breaker on primary
           n                        n                         cc
                                                                                       side (1) and (2)
          1                         2.44                     8                         S 2* D6 o K6
          1.6                       3.9                      8                         S 2* D10 o K10
          2.5                       6.1                      3                         S 2* D16 o K16
          4                         9.8                      2.1                       S 2* D20 o K20
          5                         12.2                     4.5                       S 2* D32 o K32
          6.3                       15.4                     4.5                       S 2* D40 o K40
          8                         19.5                     5                         S 2* D50 o K50
          10                        24                       5                         S 2* D63 o K63
          12.5                      30                       5                         S 2* D63 o K63

          Three-phase transformer (primary voltage 400 V)-3P, 3P+N and 4P MCBs
          P  [kVA]                  I  [A]                   u  (%)                    Circuit-breaker on primary
           n                        n                         cc
                                                                                       side (1) and (2)
          5                         7                        4.5                       S 2* D20 o K20
          6.3                       8.8                      4.5                       S 2* D20 o K20
          8                         11.6                     4.5                       S 2* D32 o K32
          10                        14                       5.5                       S 2* D32 o K32
          12.5                      17.6                     5.5                       S 2* D40 o K40
          16                        23                       5.5                       S 2* D63 o K63
          20                        28                       5.5                       S 2* D63 o K63
          S 2*.. = S 200, S 200 M, S 200 P
          (1) With modular or magnetic only circuit-breakers, without thermal adjustment, thermal protection is required for the transformer’s secondary winding.
          (2) Breaking capacity selected according to estimated Icc at the point where the breaker is installed.