          MCBs technical details
          S800 range features




                                    The S800S, -N, -C, -B and -HV high performance MCBs: safe innovation
                                    The S800 high performance MCB limits energy and current in case of a short-circuit power
                                    cutt off. The specially designed double arcing chamber system, i. e. per pole are two arcing
                                    chambers, ensures excellent operating characteristics. The new S800B has only one arcing
                                    chamber. Additional exceptional features of the S800 series are:

                                    Convincing:    Selectivity to upstream overcurrent protection devices due to a
                                                  total switch-off time of only ≤ 2.5 ms.
                                    Safe:         Excellent backup protection by limiting the energy to a value
                                                  ≤ 100 000 A s (125A /50 kA). In case of short-circuit, there is
                                                           2
                                                  a low load to the circuit and the location of the damage due to the
                                                  high limitation of the let-through energy.
                                    Loads:        Up to 125 A rated current
                                    Checked:      S series up to 50 kA rated ultimate short-circuit breaking capacity I
                                                                                                        cu
                                                  N series up to 36 kA rated ultimate short-circuit breaking capacity I
                                                                                                         cu
                                                  C series up to 25 kA rated ultimate short-circuit breaking capacity I
                                                                                                        cu
                                                  B series up to 16 kA rated ultimate short-circuit breaking capacity I
                                                                                                        cu
                                                  HV series up to 4 kA rated ultimate short-circuit breaking capacity I cu
                                    Selectable:    Characteristics:
                                    S series:     B, C, D, K, KM, UCB, UCK
                                    N series:     B, C, D
                                    C series:     B, C, D, K
                                    B series:     B, C, D, K
                                    HV series:    C, K
                                    Compact:      Slight 27 mm width per pole
                                    Flexible:     Accessories installed by the customer.

                                    S800UP, -U, -U-UCZ, -U-PVS: Highest safety now also ensured for UL applications
                                    Convincing:     Covering of different voltage ranges
                                                  (240 V AC, 480Y/277 V AC, 600 V DC, 1000 V DC)
                                    Safe:         Excellent backup protection due to limitation of energy.
                                    Loads:        Up to 100 A rated current
                                    Checked:      K-, Z series up to 50kA breaking capacity
                                                  UCZ series up to 10kA breaking capacity
                                                  PVS series up to 3kA breaking capacity
                                    Selectable:    Characteristics:
                                                  K, Z, UCZ, PVS
                                    Compact:      Smallest sizes.
                                    Flexible:     Accessories installed by the customer.
                                    Standards:    UL489, UL489B, IEC 60947-2

                                    Short description
                                    Two triggers detect overcurrents, effect the switching station and
                                    provide short-circuit protection.
                                    1.            The thermal trip for overload protection with time delay.
                                    2.            The electromagnetic fast-acting trip with concrete anchor
                                                  for short-circuit protection.
         UB
                        iD
                             t
                                    I  x √2       peak value of the prospective short-circuit current
             tk                     k
                    Un
                                    i             max. let-through current of the S800 high performance MCB
                                    D
                                    U             supply voltage
                                     n
            1 sinus half-wave       U             build up and collapse of the arc voltage
            50 Hz ⩠ T/2 = 10 ms      B
                                    t             Turn-off time of S800 high performance MCB
                                    K