Page 76 - B_ELSB_Cat_2022_01_MCBs
P. 76
1/76 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: back-up
S800B – S200M @ 230/400 V
Supply s. S800B
Char. B, C, D, K
Load s. Icu [kA]
In [A] 32 40 50 63 80 100 125*
S200M B 15 6 16 16 16 16 16 16 16
10 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16
20 16 16 16 16 16 16 16
25 16 16 16 16 16 16
32 16 16 16 16 16
40 16 16 16 16
10 50 16 16 16
63 16 16 16
Supply s. S800B
Char. B, C, D, K
Load s. Icu [kA]
In [A] 32 40 50 63 80 100 125*
S200 C, D 15 0.5…6 16 16 16 16 16 16 16
K, Z 8 16 16 16 16 16 16 16
10 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16
20 16 16 16 16 16 16 16
25 16 16 16 16 16 16
32 16 16 16 16 16
40 16 16 16 16
10 50 16 16 16
63 16 16 16
* only S800B-B,C
S800B – SN201 @ 230/240 V
Supply s. S800B
Char. B, C, D, K
Load s. Icu [kA]
In [A] 32 40 50 63 80 100 125*
SN201 B, D 10 6 16 16 16 16 16 16 16
10 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16
20 16 16 16 16 16 16 16
25 16 16 16 16 16 16
32 16 16 16 16 16
40 16 16 16 16