Page 77 - B_ELSB_Cat_2022_01_MCBs
P. 77
1
1/77
—
MCBs technical details
Coordination tables: back-up
Supply s. S800B
Char. B, C, D, K
Load s. Icu [kA]
In [A] 32 40 50 63 80 100 125*
SN201 C 10 2 16 16 16 16 16 16 16
4 16 16 16 16 16 16 16
6 16 16 16 16 16 16 16
10 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16
20 16 16 16 16 16 16 16
25 16 16 16 16 16 16
32 16 16 16 16 16
40 16 16 16 16
Supply s. S800B
Char. B, C, D, K
Load s. Icu [kA]
In [A] 32 40 50 63 80 100 125*
SN201 L B, C 6 2 16 16 16 16 15 15 15
4 16 16 16 16 15 15 15
6 16 16 16 16 15 15 15
10 16 16 16 16 15 15 15
16 16 16 16 16 15 15 15
20 16 16 16 16 15 15 15
25 16 16 16 15 15 15
32 16 16 15 15 15
40 16 15 15 15
Supply s. S800B
Char. B, C, D, K
Load s. Icu [kA]
In [A] 32 40 50 63 80 100 125*
SN201 M B 10 6 16 16 16 16 16 16 16
10 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16
20 16 16 16 16 16 16 16
25 16 16 16 16 16 16
32 16 16 16 16 16
40 16 16 16 16