1/78 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: back-up
Supply s. S800B
Char. B, C, D, K
Load s. Icu [kA]
In [A] 32 40 50 63 80 100 125
SN201 M C 10 2 16 16 16 16 16 16 16
4 16 16 16 16 16 16 16
6 16 16 16 16 16 16 16
10 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16
20 16 16 16 16 16 16 16
25 16 16 16 16 16 16
32 16 16 16 16 16
40 16 16 16 16
* only S800B-B,C
back-up values indicated in kA
S800U – S200 @ 230/400 V
Supply s. S800U
Char. K, Z
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S200 B 10 6 50 50 50 50 50 50 50 50
10 50 50 50 50 50 50 50 50
13 50 50 50 50 50 50 50 50
16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50
50 50 50 50
63 50 50
Supply s. S800U
Char. K, Z
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S200 B 10 0.5...6 50 50 50 50 50 50 50 50
8 50 50 50 50 50 50 50 50
10 50 50 50 50 50 50 50 50
13 50 50 50 50 50 50 50 50
16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50
50 50 50 50
63 50 50