Page 116 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 116

DEHNsnap
         conductor holder







                                   cap
                                basic component
         DEHNgrip
         conductor holder












       Figure 5.4.2.2  DEHNsnap and DEHNgrip conductor holders


       The DEHNhold conductor holder is made of solid stainless steel   ¨  SPANNsnap roof conductor holder with DEHNsnap plastic
       (V4A) and can be used for different materials such as Al, StSt   conductor holder or DEHNgrip stainless steel (V4A) conduc-
       (V4A), St/tZn and Cu.                           tor holder (Figure 5.4.3.2). A stainless steel (V4A) tension
       The DEHNsnap range of plastic holders (Figure 5.4.2.2) is a   spring ensures permanent tension. Universal tensioning
       basic component (roof and wall). The cap simply snaps in and   range from 180 to 280 mm with laterally adjustable con-
       fixes  the  conductor  in  the  holder,  ensuring  loose  conductor   ductor routing for 8 mm round conductors.
       routing. The special snap-in mechanism does not mechanically   ¨  FIRSTsnap conductor holder with DEHNsnap plastic con-
       stress the fastener.                            ductor holder to be fixed on existing ridge tile clips of dry
       DEHNgrip (Figure 5.4.2.2) is a screwless stainless steel (V4A)   ridges (Figure 5.4.3.3).
       holder system. This system can be used as a roof and wall con-  The FIRSTsnap conductor holder is snapped on the ridge tile
       ductor holder for conductors with a diameter of 8 mm. The   clip of dry ridges and tightened by hand (only turn DEHNsnap).
       conductor is simply pressed in to fix it in the DEHNgrip (Figure
       5.4.2.2).                                    Interlocking tiles, smooth tiles
                                                    UNIsnap roof conductor holders with pre-punched braces are
                                                    used for roof surfaces. The conductor holder is bent by hand
       5.4.3  Instructions for mounting roof conductor   before it is hooked into the pantile (Figure 5.4.3.4).
            holders
                                                    Slated roofs
       Ridge and hip tiles                          When used on slated roofs, the inner hook is bent (Figure
       The roof conductor holders are adjusted by means of a locking   5.4.3.5) or provided with an additional clamping part (Part
       screw to suit the dimensions of the ridge tile (Figure 5.4.3.1).  No. 204 089).

       In addition, conductor holders allow to gradually adjust the   Interlocking tiles
       conductor routing from the top centre to the lower side (con-  ¨  FLEXIsnap roof conductor holders for interlocking tiles are
       ductor holder can be loosened by either turning the holder or   directly pressed on the seams (Figure 5.4.3.6). The flexible
       unscrewing the locking screw).                  stainless steel (V4A) brace is pushed between the interlock-



            www.dehn-international.com                             LIGHTNING PROTECTION GUIDE  115
   111   112   113   114   115   116   117   118   119   120   121