Page 222 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 222

Anforderungsklasse B) in Hauptstromversorgungssystemen.“
       [Surge Protective Devices Type 1 – Guideline for the use of   L1   U 0  = 230 V a.c.
       surge protective devices (SPDs) Type 1 in main power supply   L2   U c  ≥ 1.1 x 230 V = 253 V a.c.
                                                       L3
       systems].                                      PEN
       This guideline published by the VDN defines basic require-          3x arrester with
                                                                           U c  ≥ 253 V a.c.
       ments which, depending on the distribution network opera-  1.1 U 0
       tor, can lead to different technical designs.                      U 0  = Phase-to-earth
       The technical design (system configuration) preferred in the          nominal a.c. voltage
       supply area must be requested from the responsible distri-
       bution network operator.
                                                                    R A
       8.1.3  Use of SPDs in TN systems             Figure 8.1.3.2  “3 – 0” circuit in a TN-C system
       In TN systems, overcurrent and residual current protective
       devices can be used for “protection against electric shock
       under fault conditions“. For the installation of SPDs, this   as residual current due to the impulse current discharged
       means that these surge protective devices may only be ar-  to PE and that it interrupts the circuit. Moreover, if a type 1
       ranged downstream of the protective devices for “protec-  SPD is stressed with partial lightning currents, it must be as-
       tion against electric shock under fault conditions” to ensure   sumed that the high dynamics of the lightning current will
       personal protection in the event of a faulty SPD.  cause mechanical damage to the residual current protective
                                                    device (Figure 8.1.3.1). This would make the protection
       If a type 1 or 2 SPD is installed downstream of a residual   measure “protection against electric shock under fault con-
       current protective device, it has to be expected that the re-  ditions” ineffective which must be avoided. Therefore, both
       sidual current protective device (RCD) interprets this process   a type 1 lightning current arrester and a type 2 SPD should
                                                    be used upstream of the residual current protective device.
                                                    Consequently, overcurrent protective devices only ensure
                                                    “protection against electric shock under fault conditions”
                                                    if type 1 and type 2 SPDs are used. SPDs may therefore only
                                                    be installed if a fuse is used as overcurrent protective de-
                                                    vice. Whether an additional separate backup fuse must be
                                                    provided in the arrester path depends on the size of the next
                                                    upstream supply fuse and the maximum permissible backup
                                                    fuse for the SPD. The maximum continuous operating volt-
                                                    ages shown in Figures 8.1.3.2 and 8.1.3.3a and b apply
                                                    to type 1, type 2 and type 3 SPDs used in TN systems.

                                                    Figure 8.1.3.4 illustrates an example of lightning current
                                                    and surge arresters in a TN-C-S system. It can be seen that
                                                    type 3 SPDs are used downstream of the residual current
                                                    protective device (RCD).
                                                    In this context, it must be noted that type 3 SPDs are pri-
                                                    marily used for differential mode protection due to the fre-
                                                    quency of switching overvoltages in the final circuits. These
                                                    overvoltages typically occur between L and N. Surge limita-
                                                    tion between L and N means that no impulse current is dis-
                                                    charged to PE. Thus, the RCD cannot interpret this process
                                                    as residual current. Moreover, type 3 SPDs are designed for
                                                    a nominal discharge capacity of 1.5 kA. These values are
                                                    sufficient if upstream protection stages of the type 1 and
                                                    type 2 SPDs discharge high-energy impulses. When using an
       Figure 8.1.3.1  RCD destroyed by lightning impulse currents  impulse-current-proof RCD, these impulse currents do not



            www.dehn-international.com                             LIGHTNING PROTECTION GUIDE  221
   217   218   219   220   221   222   223   224   225   226   227