Page 225 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 225

L1 L2 L3 NPE
                             type 3 surge arrester  type 3 surge arrester  type 3 surge arrester


                                                                                               socket outlet

                              S-Schutz

                                                   DEHNflex

                         1 x DSA 230 LA  Part No. 924 370  1 x DFL M 255  Part No. 924 396  1 x STC 230  Part No. 924 350
            cable length ≥ 5 m
                         for cable ducts         for flush-mounted systems  for existing socket outlets
           16 A
                          125 A                  125 A

                                L1  L2  L3  N          L1  L2  L3  N

                                DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  sub-distribution board
                                                                  fault indication
                                      PE                      PE


                                                 with remote signalling contact:
                         1 x DG M TNS 275  Part No. 952 400  1 x DG M TNS 275 FM  Part No. 952 405

                             type 2 surge arrester  type 2 surge arrester


                                                       DEHNbloc ®  M           DEHNventil ®
                                                                             Directly coordinated with
                             cable length ≥ 15 m    Coordinated with DEHNguard ®    type 2 and 3 Red/Line arresters
                                                    without additional cable length.
                                                                           without additional cable length.

                                 type 1             coordinated type 1           type 1
                           lightning current arrester  lightning current arrester  combined arrester
                          315 A                  315 A                   315 A

                                                     L/N  L/N  L/N          L1  L1‘  L2  L2‘  L3  L3‘
                              L1  L1’  L2  L2’  L3  L3’
                             DEHNbloc  DB 3 255 H
                                                       DEHNbloc  DB M 1 255 FM  DEHNbloc  DB M 1 255 FM  DEHNbloc  DB M 1 255 FM  DEHNventil  DV MOD 255  DEHNventil  DV MOD 255  DEHNventil  DV MOD 255  main distribution board
                                                                   fault indication
                                      N‘/PEN  N/PEN
                                                       N/PE(N)  N/PE(N)  N/PE(N)       PEN

                           1 x DB 3 255 H   Part No. 900 120  3 x DB M 1 255 FM  Part No. 961 125  1 x DV M TNC 255  Part No. 951 300
                                                  1 x MVS 1 6  Part No. 900 815  alt. 1 x DV M TNC 255 FM Part No. 951 305
                                                                        also available as
                     MEB  alt. 3 x DB 1 255 H   Part No. 900 222  alt. 3 x DB M 1 255  Part No. 961 120  1 x DV M TNS 255  Part No. 951 400
                           1 x MVS 1 6   Part No. 900 815  1 x MVS 1 6  Part No. 900 815  alt. 1 x DV M TNS 255 FM Part No. 951 405
             L1 L2 L3 PEN                       Only required, if no fuse of the same or a lower nominal value is provided in the upstream system.
          Figure 8.1.3.7  SPDs used in a TN system – Office building with separation of the PEN conductor in the main distribution board



          224  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com