Page 226 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 226

L1 L2 L3 N PE
                         type 3 surge arrester   type 3 surge arrester  type 3 surge arrester



                                                                                            socket outlet
                              Überspannungsschutz



                                                                          0  ÜBERSPANNUNGSSCHUTZ  LINE FILTER  NETZFILTER
                                                                          1  SURGE PROTECTOR  DEFECT       FUNCTION  FREQUENCY FILTER  FREQUENZFILTER
                                                        PROTECTOR
                      1 x NSM PRO EW  Part No. 924 342  1 x DPRO 230 F   Part No. 909 240  1 x SFL PRO 6X  Art.-Nr. 909 250
                                              1 x DPRO 230  Part No. 909 230
         cable length ≥ 5 m
        16 A
                       125 A                  125 A
                              L1  L2  L3              L1  L2  L3


                              DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  sub-distribution board
                                                              fault indication
                                   PEN                    PEN


                                              with remote signalling contact:
                      1 x DG M TNC 275  Part No. 952 300  1 x DG M TNC 275 FM  Part No. 952 305

                         type 2 surge arrester   type 2 surge arrester


                                                     DEHNbloc ®  M          DEHNventil ®
                                                                          Directly coordinated with
                                                 Coordinated with DEHNguard ®
                          cable length ≥ 15 m    without additional cable length.  type 2 and 3 Red/Line arresters
                                                                        without additional cable length.

                              type 1             coordinated type 1          type 1
                        lightning current arrester  lightning current arrester  combined arrester
                       315 A                  315 A                   315 A
                                                                                            main distribution board
                           L/N  L’/N’  L/N  L’/N’  L/N  L’/N’  L/N  L/N  L/N  L1  L1‘  L2  L2‘  L3  L3‘


                             DEHNbloc  DB H MOD   255  DEHNbloc  DB H MOD   255  DEHNbloc  DB H MOD   255  DEHNbloc  DB M 1 255 FM  DEHNbloc  DB M 1 255 FM  DEHNbloc  DB M 1 255 FM  DEHNventil  DV MOD 255  DEHNventil  DV MOD 255  DEHNventil  DV MOD 255
                                                                fault indication
                             N/PE(N)  N/PE(N)  N/PE(N)  N/PE(N)  N/PE(N)  N/PE(N)   PEN

                        3 x DBH M 1 255  Part No. 961 122  3 x DB M 1 255 FM  Part No. 961 125  1 x DV M TNC 255  Part No. 951 300
                        1 x MVS 1 6  Part No. 900 815  1 x MVS 1 6   Part No. 900 815
                  MEB  alt. 1 x DB 3 255 H  Part No. 900 120  alt. 3 x DB M 1 255  Part No. 961 120  alt. 1 x DV M TNC 255 FM  Part No. 951 305
                                               1 x MVS 1 6   Part No. 900 815
          L1 L2 L3 PEN                       Only required, if no fuse of the same or a lower nominal value is provided in the upstream system.
       Figure 8.1.3.8  SPDs used in a TN system – Office building with separation of the PEN conductor in the sub-distribution board



            www.dehn-international.com                             LIGHTNING PROTECTION GUIDE  225