Page 224 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 224

external LPS  lightning current arrester  sub-distribution board  surge arrester terminal devices
                           main distribution board


                                             protection as per IEC 62305 (EN 62305)
                                                           protection as per IEC 60364-4-443
                           F1
                                                                                         L1
                                                                                         L2
                                                                        RCD
                                            Wh                                           L3
                                                                                         N
                          SEB
                                                                                         PE
                                          F2                        F3







                               MEB                            local EBB




       Figure 8.1.3.5  SPDs used in a TN-S system

           L1 L2 L3 NPE
                          type 3 surge arrester                          type 3 surge arrester

                                              heating controller                            socket outlet
                              1  2
                                  heating
                               DEHNrail  DR M 2P 255 FM
          cable length ≥ 5 m                                                   P ROTECTOR

                                                                     1 x DPRO 230
                                                                     1 x DPRO 230 F   Part No. 909 230
                                                                                 Part No. 909 240
                       1 x DR M 2P 255  Part No. 953 200             1 x SFL PRO  Part No. 912 260
         16 A
             KW h
                                                                      As an alternative, surge arresters
                                                type 1 combined arrester  (e.g. DG M TNC 275  Part No. 952 300)
                           L1  L1'  L2  L2'  L3  L3'
                                                                      can also be used downstream of meter
                                                                      panels if there is no
                              DEHNventil  DV MOD 255  DEHNventil  DV MOD 255  DEHNventil  DV MOD 255  – lightning protection system
                                                                      – electrical power supply via the service   central MDB / SDB
                                                                        entry mast
                                                                      – antenna of the roof
                                      PEN
                                               1x DV M TNC 255          Part No. 951 300  – if none of the conditions mentioned
                                            alt. 1x DV M TNC 255 FM  Part No. 951 305    above applies to an adjoining building
         ≤ 315 A
                       MEB
            L1 L2 L3 PEN
       Figure 8.1.3.6  SPDs used in a TN system – Single-family house



            www.dehn-international.com                             LIGHTNING PROTECTION GUIDE  223