Page 342 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 342

earthing
                                                                               conductor


                                                        depth in the ground
                                                        of at least 0.5 m
               conductor in contact with the
               ground, corrosion-resistant
                                                        distance of at
                                                        least 0.5 m
                                                                protective angle
                                                                  of max. 90 °
                                          0.5 m
                        preferably 0.5 m
                    feeder cable                                cable with current carrying shield


       Figure 9.15.4  Earthing conductor for protecting the cable route and   Figure 9.15.5  Protected volume of a cable route
                earthing the mast


       In case of new installations where the masts and cables have   If lightning hits the mast (not the mast light itself) or the
       not been installed yet, a bare earthing conductor is to be in-  ground, the earthing conductor assumes the function of the
       stalled above the cable route.               required earth electrode and linearises the potential drop,
                                                    thus preventing flashover to the cable (Figures 9.15.4 and
                                                    9.15.5).





































            www.dehn-international.com                             LIGHTNING PROTECTION GUIDE  341