Figure 5.1.12.3  Integration of the safety rope system (fall protection) in the air-termination system

                                                       Incorrect installation
                                                       Figure 5.1.12.2 shows a negative example which unfortu-
                                                       nately can often be found in practice today. This safety rope
                                                       system was positioned above the lightning protection system.
                                                       It is also questionable whether the conventional connecting
                                                       clamp for contacting the safety rope system used in this ex-
                                                       ample is capable of carrying lightning currents. The cable used
                                                       to connect the safety rope system and the meshed network
                                                       is very short. If a person falls from the roof, the safety rope
                                                       system can be lowered up to 1 m to compensate the fall. The
                                                       too short connecting cable shown in Figure 5.1.12.2 would
          Figure 5.1.12.4  Flat-roofed structure – Detailed view










                                                     approx. 1.5 m








                                                             Safety rope system (stainless steel)
                                                washer       Intermediate support / support point
                                                             Connection set, safety rope system with
                                                             Terminal lug, connection of the safety rope system and
                                                             Clamping frame, connection to the air-termination system
            tightening torque  tightening torque
            1 x M10, 20 Nm    2 x M6, 5 Nm                   Roof conductor holder
          Figure 5.1.12.5  Installation example: Connecting set for safety rope systems