Page 35 - Arc Guard System - TVOC-2
P. 35

ABB  ARC GUARD SYSTEM™ – TVOC-2  INSTALLATION AND MAINTENANCE GUIDE                35




               INFORMATION                                    4.3.2.2  Arc detection
               After completed Start-Up Sequence at the       To check the detectors and the Arc Monitor, simulate an
               first time installation the complete sytem     arc by using a camera flash, repeat the following steps:
               needs checking.
               This includes checking that the detectors and
               HMI works as intended.
                                                              1.     Set the camera flash to approximately 0.5 ms.
               See: “4.3.1 Start-Up Sequence” on page 33.
                                                              2.     Place the camera flash at a distance between
          4.3.2    Check                                             1.5 - 2 meters (60-80 inches) from the detector.
                                                              3.     Make sure no object is standing in the way.
               INFORMATION
               Do the test after installation and before the Arc   4.   Point the camera flash towards the detector.
               Monitor is used!
                                                              5.     Press the flash test button.
               This test is done for each installed detector
               and the Arc Monitor.The test will check that                                                           04
               the detectors react to a simulated arc and the   6.   Carry out the following steps to check the Arc
               HMI will display a notification window showing        Monitor
               which detector and which circuit breaker is
               tripped. The breaker that is connected to the         a. Check the HMI display.
               Arc Monitor should trip. Use a camera flash to
               simulate an arc. At normally sensitivity the Arc      b. If the detector reacts correctly and causes
               Monitor will react to the flash.                      a trip then it should show on the HMI display as a
               INFORMATION                                           notification window.
               Flash specifications to simulate an arc, 16 (m)       c. The notification window shows, Trip has
               guide no. 21 DIN/100 ASA.                             Occurred, which detector, which trip contact, at
                                                                     what time and date.

          4.3.2.1  Sensor supervision (E6-S extension module)        d. The breaker that is connected to the Arc
                                                                     Monitor should trip, depending on the
                                                                     configuration.
          Check that the sensor supervision is working for each of
          the 10 detectors with the following steps:
                                                                     e. At the notification window, if manual reset
                                                                     is configured, press Reset. If auto reset is
          1.     Force an error by removing either the detector
                 head, the detector cable or a dummy plug.           configured, press Menu.

          2.     Check the HMI: When the error is applied
                 the system error popup shall be displayed within
                 30 seconds on the HMI showing the bit for
                 sensor supervision error and by pressing page
                 down the correct detector shall be marked with a
                 zero (0) for faulty detector.
   30   31   32   33   34   35   36   37   38   39   40