Page 30 - Arc Guard System - TVOC-2
P. 30

30               ABB  ARC GUARD SYSTEM™ – TVOC-2  INSTALLATION AND MAINTENANCE GUIDE




          DIP switch 3 to position ON and DIP switch 4 to
          position 0.                                                                          43 44  53 54  63 64

          Set DIP switch 3 to position ON and DIP switch 4 to       O  1 2 34 56 7 8           Trip K4  K5 Trip  Trip K6
                                                                    N
          position 0.
                                                                                        X3
          •  Detectors X1: 1-3 operate trip contact K4.                                 X2
                                                                                        X1
          •  Detectors X1: 4-6 operate trip contact K5.                      43 44  53 54  63 64  43 44  53 54  63 64
          •  Detectors X1: 7-10 and all detectors on X2 and X3,              K4 Trip  K5 Trip  K6 Trip  K4  K5  K6
            operate trip contact K6.                                                          Trip  Trip  Trip
                                                                      X3               X3
                                                                      X2               X2
                                                                      X1               X1


                                                                                                    1SFC170011M0201

                                                              Figure 32
                                                              DIP switch 3 to position ON, DIP switch 4 to position 0
          Manual/Auto reset configuration
   04
          The signal relays K2 and K3 can be configurated to react as
          trip contacts (auto reset) or to be de-energized by manual
          reset on the HMI.
                                                                                 Detector
          Configuration Auto reset, set DIP switch 6 to position ON.    O  1 23 45 6 7 8
                                                                N                K 4-6        250 ms
          Configuration Manual reset, set DIP switch 6 to position 0.
                                                                                 K 2-3



                                                                                                     1SFC170011M0201
                                                              Figure 33
                                                              Configuration Auto reset




                                                                                Detector

                                                               O  1 23 45 6 7 8  K 4-6       250 ms
                                                               N
                                                                                K 2-3

                                                                             Manual reset


                                                                                                     1SFC170011M0201

                                                              Figure 34
                                                              Configuration Manual reset
          Current Sensing Unit (option)
          DIP switch (A) 1 and 2 configure the CSU-2 input (B) 21, 22
          to the Arc Monitor.



                                                                    A




                                                                                           B
                                                                                                     1SFC170011M0201
                                                              Figure 35
                                                              Current sensing unit (option)
   25   26   27   28   29   30   31   32   33   34   35