Page 31 - Arc Guard System - TVOC-2
P. 31

ABB  ARC GUARD SYSTEM™ – TVOC-2  INSTALLATION AND MAINTENANCE GUIDE                31




          No CSU-2 connected
          When there is no CSU-2 connected to the Arc Monitor then
          set the DIP switch 1 and 2 to position 0.
          DIP switch 1 and 2 in position 0 is the default state   A                   B
          (factory settings).                                    O  1 2 34 56 7 8
                                                                 N







                                                                                                     1SFC170011M0201
                                                              Figure 36
                                                              No CSU-2 connected
          One (1) CSU-2 connected
          If there is one (1) CSU-2 connected to the CSU-2 input X1,                                                  04
          21 then set the DIP switch 1 to position ON.



                                                                 O  1 2 34 56 7 8
                                                                 N






                                                                                                     1SFC170011M0201
                                                              Figure 37
                                                              One CSU-2 connected
          DIP switches 1, 2, 3 and 4 to position ON
          Set DIP switches 1, 2, 3 and 4 to position ON. In this
          configuration two CSU-2 are connected.
          For more information See: “Two (2) CSU-2 connected” on
          page 31.                                                                   43 44  53 54  63 64  43 44  53 54  63 64
          •  Any detector with combination of over current      O  1 23 4 56 7 8     Trip K4  Trip K5  Trip K6  K4 Trip  Trip K5  Trip K6
            condition in CSU-2 21, operates trip contacts K4 and   N           X3 X2           X3 X2
            K6. As well as signal relays K2 and K3.                            X1              X1
                                                                                       CSU              CSU
          •  Any detector with combination of over current
            condition in CSU-2 22, operates trip contacts K5 and
            K6. As well as signal relays K2 and K3.
                                                                                                     1SFC170011M0201
                                                              Figure 38
                                                              DIP switches 1,2,3 and 4 to position ON
          Two (2) CSU-2 connected

          If there are two (2) CSU-2s connected to the CSU-2 input
          21 and 22 then set the DIP switch 1 and 2 to position ON.

               WARNING
                                                                 O  1 2 34 56 7 8
               The CSU-2 cable is connected before               N
               configuration is made.
               For more information how to connect CSU-2
               cables, See: “Connecting CSU-2 cable” on page
               24.

                                                                                                     1SFC170011M0201
                                                              Figure 39
                                                              Two CSU-2 connected
   26   27   28   29   30   31   32   33   34   35   36