5/122            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          Telecoms & computer line protection
          OVR KT & KE Series






  5
                                            Combined Category D, C, B tested protector (to BS EN 61643) suitable for use
                                            on ten line LSA-PLUS disconnection modules to PBX telephone exchanges, ISDN
                                            and other telecoms equipment with LSA-PLUS disconnection modules. For use
                                            at boundaries up to LPZ 0 to protect against flashover (typically the service
                                            entrance location) through to LPZ 3 to protect sensitive electronic equipment.


          Features & benefits
          •  Low cost protection for large numbers of data and signal   •  At larger installations OVR K10T1 and OVR K10T1/PTC
           lines                                               provide all in one protection for all ten lines on LSA-PLUS
          •  Very low let-through voltage (enhanced protection to    disconnection modules
           IEC/BS EN 62305) between all lines - Full Mode protection  •  Use the OVR KE10 to provide trouble free earthing for
          •  Full Mode design capable of handling partial lightning   up to ten OVR KT1 and OVR KT1/PTC (per disconnection
           currents as well as allowing continual operation of   module)
           protected equipment                                •  OVR K10T1 and OVR K10T1/PTC have an integral earth
          •  Repeated protection in lightning intense environments  connection, and an external M4 earth bush for use with
          •  Colour of housing distinguishes electrically different   non-metallic LSA-Plus frames
           protectors - avoids confusion when installed together    •  OVR KT1/PTC and OVR K10T1/PTC have resettable
           on the same distribution frame                      overcurrent protection and are rated for power cross faults
          •  Quick and easy plug-in installation, with ‘bump’    •  OVR KT1, OVR KT1/PTC, OVR K10T1 and OVR K10T1/PTC are
           location feedback                                   suitable for telecoms applications in accordance with
          •  Under power line cross conditions/PTC versions offer safe   Telcordia and ANSI Standards
           disconnection during fault duration. Unit auto-resets once
           fault corrected


          Application                                         Installation
          •  For PSTN (e.g POTS, dial-up, lease line, T1/E1,   Install protectors on all lines that enter or leave each
           *DSL and Broadband) and U interface ISDN lines, use OVR   building (including extensions to other buildings). Identify
           KT1 (or OVR KT1/PTC) and OVR K10T1 (or OVR K10T1/PTC)  the lines requiring protection and plug-in the protector
          •  Protect single lines with OVR KT1 or OVR KT1/PTC  (ensuring the correct orientation) for a series connection.
          •  Protect all ten lines on a disconnection module with   Plug OVR K10T1 or OVR K10T1/PTC directly into each
           OVR K10T1 or OVR K10T1/PTC                         disconnection module requiring protection.

                                                              OVR KT1 and OVR KT1/PTC must be installed via the OVR
                                                              KE10 earth bar. Clip an OVR KE10 on to the disconnection
                                                              module and plug an OVR KT1 or OVR KT1/PTC in to each line
                                                              on the module that needs protecting. In the unlikely
                                                              situation that the protector is damaged, it will sacrifice
                                                              itself and fail short circuit, taking the line out of
                                                              commission, indicating it needs replacing and preventing
                                                              subsequent transients from damaging equipment.

                                                              For further information on global telephony applications,
                                                              see separate Application Note OVR AN005 (contact us for
                                                              a copy).





          NOTE: For individual telephone lines and lines at unmanned sites the high performance OVR TN or plug-in OVR TN/JP or OVR TN/RJ11 Series should be used.
          For plug-in S/T interface ISDN protection, use the ISDN Series protectors.