          Protection and safety
          Data & signal protection
          OVR TN, TNQ & SL TN Series


          OVR TN, TNQ & SL TN Series - Technical specification
          Electrical specification            OVR TN           OVR SL TN, OVR SL TNL           OVR TNQ
          ABB order code                      7TCA085400R0345  7TCA085400R0323, 7TCA085400R0418  7TCA085400R0344       5
          Nominal voltage  (1)                –
          Maximum working voltage Uc (RMS/DC)  (2)  –/296 V
          Current rating (signal)             300 mA
          In-line resistance (per line ±10%)  4.4 Ω
          Bandwidth (-3 dB 50 Ω system)       20 MHz
          Transient specification             OVR TN           OVR SL TN , OVR SL TNL          OVR TNQ
                                    (3)
          Let-through voltage (all conductors)   Up
          C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to    395 V
          BS EN/EN/IEC 61643-21
          C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to    390 V
          BS EN/EN/IEC 61643-21
          B2 test 4 kV 10/700 μs to BS EN/EN/IEC 61643-21  298 V
          5 kV, 10/700 μs  (4)                300 V
          Maximum surge current
          D1 test 10/350 μs to    – Per signal wire  2.5 kA    1.25 kA                         2.5 kA
          BS EN/EN/IEC 61643-21  – Per pair   5 kA             2.5 kA                          5 kA
          8/20 μs to ITU-T K.45:2003,   – Per signal wire  10 kA
          IEEE C62.41.2:2002   – Per pair     20 kA
          Mechanical specification            OVR TN           OVR SL TN , OVR SL TNL          OVR TNQ
          Temperature range                   -40 to +80 °C
          Connection type                     Screw terminal -   Screw terminal - max. torque 0.8 N  Pluggable 12 way screw
                                              max. torque 0.5 Nm                               terminal
          Conductor size (stranded)           2.5 mm   2       4 mm   2                        2.5 mm 2
          Earth connection                    M6 stud          Via DIN rail or 4 mm  earth terminal -    Via DIN rail or M5
                                                                             2
                                                               max. torque 0.8 Nm              threaded hole in base
                                                                                               of unit
          Case Material                       FR Polymer UL-94 V-0
          Weight            – Unit            0.08 kg                                          0.1 kg
                            – Packaged (per 10)  0.85 kg                                       1.3 kg
          Dimensions                          See diagram below



                                            OVR TN                                 OVR TNQ           95 mm

                                                                              54 mm
                                                   38 mm                                        M3 clearance
                                                                                                Depth: 18 mm
                                                                105 mm                   87 mm            69 mm
                                                               M4 clearance
                                                                                                     42 mm
                                                                120 mm
                                                   19 mm
                                                                109 mm
                                                               M4 clearance        OVR SL TN
          (1)   Nominal voltage (RMS/DC or AC
           peak) measured at < 10 μA
          (2)   Maximum working voltage (RMS/DC
                                                                                                            104.6 mm
           or AC peak) measured at < 5 mA
          (3)   The maximum transient voltage let-through of the
           protector throughout the test (±10%), line to line &            106.5 mm
           line to earth, both polarities. Response time < 10 ns
          (4)   Test to IEC 61000-4-5:2006, ITU-T (formerly
                                                             7 mm    2  S  1         1  S  2  E
           CCITT) K.20, K.21 and K.45,Telcordia
           GR-1089-CORE, Issue 2:2002, ANSI TIA/EIA/
           IS-968-A:2002 (formerly FCC Part 68)