Page 567 - Din prodcuts 2020
P. 567

5/123




          —
          Protection and safety
          Telecoms & computer line protection
          OVR KT & KE Series


          OVR KT & KE Series - Technical specification
          Electrical specification       OVR KT1       OVR KT1/PTC    OVR K10T1      OVR K10T1/PTC
          ABB order code                 7TCA085400R0305 7TCA085400R0306 7TCA085400R0307 7TCA085400R0410               5
          Maximum working   – line to line  296 V      296 V          296 V          296 V
          voltage Uc  (1)
                           – line to earth  296 V      296 V          296 V          296 V
          Current rating (signal)        300 mA        145 mA         300 mA         145 mA
          In-line resistance (per line ±10%)  4.4 Ω
          Bandwidth (-3 dB 50 Ω system)  20 MHz        20 MHz         20 MHz         20 MHz
          Transient specification        OVR KT1       OVR KT1/PTC    OVR K10T1      OVR K10T1/PTC
          Let-through voltage (all conductors)   Up
                                    (2)
          C2 test 4 kV 1.2/50 μs,  – line to line  395 V  395 V       395 V          395 V
          2 kA 8/20 μs to BS   – line to earth  395 V  395 V          395 V          395 V
          EN/EN/IEC 61643-21
          C1 test 1 kV, 1.2/50 μs,  – line to line  390 V  390 V      390 V          390 V
          0.5 kA 8/20 μs to BS   – line to earth  390 V  390 V        390 V          390 V
          EN/EN/IEC 61643-21
          B2 test 4 kV 10/700 μs  – line to line  298 V   298 V       298 V          298 V
          to BS EN/EN/IEC   – line to earth  298 V     298 V          298 V          298 V
          61643-21
                     (3)
          5 kV, 10/700 μs     – line to line  300 V    300 V          300 V          27 V
                           – line to earth  300 V      300 V          300 V          80 V
          Maximum surge current  (4)
          D1 test 10/350 μs to   – line to line  1 kA
          BS EN/EN/IEC     – line to earth  2 kA
          61643-21
          8/20 μs to ITU-T   – line to line  5 kA
          K.45:2003, IEEE   – line to earth  10 kA
          C62.41.2:2002
          Power Faults specification     OVR KT1       OVR KT1/PTC    OVR K10T1      OVR K10T1/PTC
          Power/Line Cross and Power Induction - tests to: ITU-T (formerly CCITT) K.20, K.21 and
          K.45, Telcordia GR-1089-CORE, Issue 2:2002, UL 60950/IEC 950
          Power/line cross               –             110/230 Vac     –              110/230 Vac
                                                       (15 min)                      (15 min)
          Power induction                –             600 V, 1 A (0.2 sec)   –       600 V, 1 A
          Mechanical specification       OVR KT1, OVR KT1/PTC         OVR K10T1, OVR K10T1/PTC     OVR KE10
          Temperature range              -40 to +80 °C                                              –
          Connection type                To LSA-PLUS disconnection modules (BT part number 237A)    –
          Earth connection               Via OVR KE10 earth bar       Via integral earth clip/external M4 bush   –
          Material                       FR Polymer UL-94 V-0                                      Stainless Steel
          Weight           – Unit        0.01 kg                      0.10 kg                      0.01 kg
                           – Packaged    0.12 kg (per 10)             0.12 kg                      0.10 kg (per 10)
          Dimensions                     See diagram below





                                                        22 mm
                                                                                                   110 mm
                                                             40 mm
          (1)   Maximum working voltage (DC or          40 mm
           AC peak) at 10 μA for OVR KT1, OVR KT1/  59 mm                        59 mm  20 mm
           PTC, OVR K10T1, OVR K10T1/PTC
          (2)   The maximum transient voltage let-through of the
                                                                                                 Depth: 21 mm
           protector throughout the test (±10%), line to line &   9.5 mm  110 mm  22 mm
           line to earth, both polarities. Response time < 10 ns
          (3)   Test to IEC 61000-4-5:2006, ITU-T (formerly
           CCITT) K.20, K.21 and K.45,Telcordia
           GR-1089-CORE, Issue 2:2002, ANSI TIA/EIA/
           IS-968-A:2002 (formerly FCC Part 68)
          (4)   The installation and connections external to the
           protector may limit the capability of the protector