5/128            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          Telecom & computer line protection
          OVR Cat-5 & Cat-6 Series






  5
                                            Combined Category D, C, B tested protector (to BS EN 61643) suitable to
                                            protect twisted pair Ethernet networks, including Power over Ethernet (PoE),
                                            with RJ45 connections. For use at boundaries up to LPZ 0 to protect
                                            against flashover (typically the service entrance location) through to LPZ 3
                                            to protect sensitive electronic equipment.


          Features & benefits
          •  Suitable for systems signalling on up to eight wires of   •  Low capacitance circuitry prevents the start-up signal
           either shielded or unshielded twisted pair cable   •   degradation associated with other types of network
          •  Very low let-through voltage (enhanced protection to    protector
           IEC/BS EN 62305) between all lines - Full Mode design   •  Low in-line resistance minimizes unnecessary reductions
           capable of handling partial lightning currents as well as   in signal strength to maximize signalling distance
           allowing continual operation of protected equipment  •  Sturdy ABS housing with convenient holes for flat
          •  Repeated protection in lightning intense environments  mounting, or vertically via TS35 ‘Top Hat’ DIN rail
          •  Unlike some competing devices, the ethernet SPDs    •  Substantial earth connection to enable effective earthing
           provide effective protection without impairing the   •  Will protect all PoE powering modes A and B.
           system’s normal operation


          Application
          Use these protectors on network cables that travel between   •  To protect up to 100baseT Power over Ethernet (PoE)
          buildings to prevent damage to equipment, e.g. computers,   networks with Cat-5/Cat-5e use OVR Cat-5e/PoE
          servers, repeaters and hubs. Suitable for computer networks   •  To protect up to 1000baseT/10GbaseT Power over
          up to Cat-6A cabling.                                Ethernet (PoE) networks with Cat-6/Cat-6A cabling use
          •  To protect up to 100baseT networks with Cat-5/Cat-5e   OVR Cat-6/PoE
           cabling use OVR Cat-5e
          •  To protect up to 1000baseT/10GbaseT networks with    For further application information, see separate
           Cat-6/Cat-6A cabling use OVR Cat-6                 Application Note OVR AN004 (contact us for a copy).


          Installation
          Connect in series with the network cable, either:
          •  Near to where it enters or leaves the building, or
          •  As it enters the network hub, or
          •  Close to the equipment being protected           Accessories
          This should be close to the system’s earth star point    OVR CAT5e/UTP-1      OVR CAT6/STP-2
                                                              1 metre cable with unshielded
                                                                                        2 metre screened cable with
          (to enable a good connection to earth).             RJ45 connections          shielded RJ45 connections



                                                              Plug-in series connection       TECHNICAL NOTE: The
                                                                                              interfaces used in Ethernet
                                                               DIRTY                                           CLEAN  networks incorporate an
                                                                                              isolation transformer which
                                                                                              gives these systems an in-
                                                                                              built immunity to transients
                                                                From               To         between line and earth
                                                                line               equipment  of 1,500 Volts or more.
                                                                       Earth





          NOTE: To protect datacomms systems based on twisted pairs, use the OVR D, E or H Series. Local protection for networked equipment is also available.