5/128 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
Protection and safety
Telecom & computer line protection
OVR Cat-5 & Cat-6 Series
5
Combined Category D, C, B tested protector (to BS EN 61643) suitable to
protect twisted pair Ethernet networks, including Power over Ethernet (PoE),
with RJ45 connections. For use at boundaries up to LPZ 0 to protect
against flashover (typically the service entrance location) through to LPZ 3
to protect sensitive electronic equipment.
Features & benefits
• Suitable for systems signalling on up to eight wires of • Low capacitance circuitry prevents the start-up signal
either shielded or unshielded twisted pair cable • degradation associated with other types of network
• Very low let-through voltage (enhanced protection to protector
IEC/BS EN 62305) between all lines - Full Mode design • Low in-line resistance minimizes unnecessary reductions
capable of handling partial lightning currents as well as in signal strength to maximize signalling distance
allowing continual operation of protected equipment • Sturdy ABS housing with convenient holes for flat
• Repeated protection in lightning intense environments mounting, or vertically via TS35 ‘Top Hat’ DIN rail
• Unlike some competing devices, the ethernet SPDs • Substantial earth connection to enable effective earthing
provide effective protection without impairing the • Will protect all PoE powering modes A and B.
system’s normal operation
Application
Use these protectors on network cables that travel between • To protect up to 100baseT Power over Ethernet (PoE)
buildings to prevent damage to equipment, e.g. computers, networks with Cat-5/Cat-5e use OVR Cat-5e/PoE
servers, repeaters and hubs. Suitable for computer networks • To protect up to 1000baseT/10GbaseT Power over
up to Cat-6A cabling. Ethernet (PoE) networks with Cat-6/Cat-6A cabling use
• To protect up to 100baseT networks with Cat-5/Cat-5e OVR Cat-6/PoE
cabling use OVR Cat-5e
• To protect up to 1000baseT/10GbaseT networks with For further application information, see separate
Cat-6/Cat-6A cabling use OVR Cat-6 Application Note OVR AN004 (contact us for a copy).
Installation
Connect in series with the network cable, either:
• Near to where it enters or leaves the building, or
• As it enters the network hub, or
• Close to the equipment being protected Accessories
This should be close to the system’s earth star point OVR CAT5e/UTP-1 OVR CAT6/STP-2
1 metre cable with unshielded
2 metre screened cable with
(to enable a good connection to earth). RJ45 connections shielded RJ45 connections
Plug-in series connection TECHNICAL NOTE: The
interfaces used in Ethernet
DIRTY CLEAN networks incorporate an
isolation transformer which
gives these systems an in-
built immunity to transients
From To between line and earth
line equipment of 1,500 Volts or more.
Earth
NOTE: To protect datacomms systems based on twisted pairs, use the OVR D, E or H Series. Local protection for networked equipment is also available.